| 2008-09-26 16:27:02 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. FOR RECORD RETENTION PER |
| | 106.5 FBC, AND CLARITY IN THE FIELD WHEN WORKING FROM |
| | THIS DOCUMENT, PLEASE INDICATE THE CODE CYCLES UNDER |
| | WHICH THIS PLAN WAS DESIGNED. ***SEE NOTE #1 SHEET |
| | E2.1. |
| | |
| | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). CIRCUITS 1,4,8 AND 10 PANEL |
| | "B" AND CIRCUITS 9 AND 10 IN PANEL "A" HAVE THESE |
| | CIRCUITS ON 15 AMP OCP AND #14 CONDUCTORS. |
| | |
| | 3} THE DINING ROOM CIRCUIT #6 IN PANEL "A" IS REQUIRED |
| | TO BE ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1). |
| | |
| | 4} THE CIRCUIT BREAKER, OCP, FOR CIRCUIT #24 GARAGE |
| | DOOR OPENER, PANEL "A" IS INCORRECTLY LABELED 10 AMP. |
| | SEE 240.6(A) FOR STANDARD RATINGS. |
| | |
| | NOTE: IN THE CALCULATION SUB TOTALS THE DIVIDER IS |
| | SHOWN AS 24 VOLTS, BUT CORRECTLY CALCULATED USING 240 |
| | VOLTS. |
| | |
| | 5} 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| | SHALL HAVE BATTERY BACK UP. |
| | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN. |
| | NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.*** |
| | REVISE SHEET E1.2 FOR COMPLIANCE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |