| 2009-09-02 16:51:54 | BUILDING PLAN REVIEW |
| | PERMIT: 08090412 |
| | ADD: 1610 PALM BEACH LAKES |
| | CONT: CFR COASTAL |
| | TEL: (954) 868-9692 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | WEDNESDAY SEPTEMBER 02/2009 |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS, |
| | REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL |
| | REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD |
| | BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE |
| | REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004 |
| | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE |
| | CODE. |
| | |
| | 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER |
| | BUILDING DATA DOES NOT PROVIDE AS TO WHAT CODE (YEAR) |
| | THIS PROJECT WAS DESIGNED. |
| | |
| | 1E) PLEASE CORRECT. STRUCTURAL SHEET S.02 ALSO NEEDS TO |
| | BE UPDATED TO THE 2007 SUPPLEMENTS CURRENTLY READS 2006 |
| | SUPPLEMENTS.. |
| | |
| | 1F) 2ND REQUEST, SP.01 CALCULATIONS THE BUILDING |
| | INFORMATION AND CODE SECTIONS ARE NOT TAKEN FROM THE |
| | 2004 FBC PLEASE PROVIDE THE FOLLOWING BUILDING |
| | INFORMATION IN REGUARDS TO THE 2004 FBC: |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) TYPE OF OCCUPANCY, SHEET SP.01 INDICATE A A2 |
| | OCCUPANCY, SECTION 303.1 INDICATES AN A2 OCCUPANCY IS |
| | RESTARAUNT, NIGHTCLUBS, BANQUET HALL, BARS AND |
| | NIGHTCLUBS PLEASE SEE A3 OCCUPANCY OF COMMUNITY HALLS, |
| | CHURCHES &AND COURT ROOMS, PLEASE REVISE. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, |
| | CHAPTER 6, & TABLE 601, SP.01 CALCULATIONS INDICATE |
| | THIS TO BE A TYPE V-B / A-3 ASSEMBLY WITH 115373 SQ FT |
| | A TYPE V-B BUILDING WITH AREA INCREASESAND SPRINKLER |
| | THE MAXIMUM IS 28,500 SQ FT.. PLEASE CORRECT. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | H) SP.01- REFRENCES A 4 HR FIRE SEPERATION WALL WITH 3 |
| | HR OPENING PROTECTIVES IS THIS AN ADDITION OR IS THIS A |
| | TRUE 4 HR FIRE WALL CREATING 2 SEPERATE BUILDINGS? I |
| | BELIEVE THE ELECTRICAL PLAN REVIEWERR HAD BROUGHT UP |
| | MANY PROBLEMS IN THE ELECTRICAL DESIGN IF THIS WAS TO |
| | BE CONSIDERED A SEPERATE BUILDING? |
| | . |
| | 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD |
| | BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S. |
| | S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) SUBMIT:SEMI-COMPLIED, SUBMITTED SPECIAL INSPECTOR |
| | AGREEMENT. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 |
| | W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR |
| | THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY |
| | FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM |
| | INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN CONRAD |
| | MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| | (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 2C) COMPLIED. |
| | |
| | 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS |
| | REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR |
| | WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR |
| | RATED OPENING. THERE IS A SECOND SWING DOOR WITHIN THE |
| | 4 HR RATED WALL AND A NOTE INDICATING ALL DOORS WITHIN |
| | THE HALLWAY TO BE 45 MINUTE RATED DOORS. THE OCCUPANCY |
| | SEPERATION INDICATED IN TABLE 302.3.2 A 3HR FIRE RATING |
| | AND 3 HR OPENING PROTECTIVES TABLE 715.3. THE EXISTING |
| | BREAK ROOM DOOR SHOULD READ 3 HR OPENING PROTECTIVE. |
| | LS.01 ALSO INDICATES AN EXIT LIGHT THAT LEADS YOU BACK |
| | INTO THE BUILDING, PLEASE PROVIDE RATIONAL . |
| | |
| | 3B) COMPLIED. |
| | |
| | 3C) COMMENT 3A) COVERS THIS OPENING. |
| | |
| | 4) BUILDING PROVISO: |
| | 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 5) BUIULDING PROVISO: |
| | 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL |
| | FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE |
| | UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A |
| | HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE |
| | WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED |
| | FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER |
| | AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO |
| | PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO |
| | FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A |
| | HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A |
| | FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A |
| | LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE |
| | SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS |
| | CHAPTER. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 & |
| | A.06 DETAIL# 1DOES NOT PROVIDE INFORMATION AS TO TYPE |
| | OF ROOFING ASSEMBLIES TO BE APPLIED TO THE FLAT DECK. |
| | |
| | |
| | 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9-15 ) COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |