| Date |
Text |
| 2009-01-28 16:46:10 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| | THE FOLLOWING INFORMATION: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, PRESSURE NOT INDICATED. |
| | |
| | E. OK |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT MANUF SHEETS FOR THE WATER |
| | HEATER NOT SUBMITTED. |
| | |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND |
| | THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE |
| | EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER |
| | HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL? |
| | PLEASE CLARIFY. |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | |
| | 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 604. |
| | ****RESPONSE NOTED. BUT THE PIPING TO THE P-6 SINK |
| | STILL DOES NOT REFLECT THE FLOOR PLAN AS INDICATED. |
| | PLEASE CORRELATE. ALSO THE WATER HAMMER ARRESTORS SHALL |
| | BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", |
| | NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201. |
| | |
| | 12. OK |
| | 13. OK |
| | |
| | 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT |
| | MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX |
| | (561) 659-7458 - E-MAIL [email protected]. ARTICLE III |
| | SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON |
| | INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT. |
| | ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR A 1250 |
| | GAL INTERCEPTOR AND THE PLANS SHOW A 750 GAL |
| | INTERCEPTOR. PLEASE SHOW REQUIRED SIZE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |