| Date |
Text |
| 2009-01-28 16:36:08 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| | THE FOLLOWING INFORMATION: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, BUT DELEVERY PRESSURE IS NOT |
| | INDICATED. |
| | |
| | E. OK |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE GAS |
| | WATER HEATER HAVE NOT BEEN SUBMITTED. |
| | |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE, NOTED, BUT THE MANUAL SHUT OFF VALVE AND |
| | THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE |
| | EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER |
| | HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL? |
| | PLEASE CLARIFY. |
| | |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |