| Date |
Text |
| 2009-01-28 16:18:00 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT |
| | THE FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. LENGHTS NOT SHOWN. |
| | |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000. |
| | |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. FOR WATER HEATER. |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 2. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES |
| | NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE |
| | RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES |
| | ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 & |
| | 402. |
| | |
| | 3. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION |
| | OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS |
| | 408.2 & 408.4. |
| | |
| | 4. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING |
| | BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH |
| | SHEET. FAC 61B15-23.002(2) & FS 471.025. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |