| 2008-09-26 09:35:55 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PLEASE PROVIDE A DETAIL ON HOW THE 1000 GAL U/G |
| | PROPANE TANK FITTING HOUSING, HOUSING COVER, TANK |
| | CONNECTIONS AND PIPING ARE TO BE PROTECTED AGAINST |
| | VEHICULAR DAMAGE IN THE DRIVEWAY. PER NFPA CHAPTER 58, |
| | SECTION 6.6.6.1 (B) (C) (D) (E). |
| | |
| | 2. PLEASE KNOW THAT THE 1000 GAL PROPANE TANK DETAIL IS |
| | NOT LEGIBLE. PLEASE PROVIDE A DETAIL THAT IS LEGIBLE |
| | AND CLARIFIES IF THE PROPANE TANK IS AN ASME APPROVED |
| | NONINTERCHANGABE UNDERGROUND CONTAINER OR AN APPROVED |
| | INTERCHANGABLE ABOVEGROUND-UNDERGROUND CONTAINER. PER |
| | (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |