Plan Review Notes
Plan Review Notes For Permit 08090396
Permit Number 08090396
Review Stop B
Sequence Number 2
Notes
Date Text
2008-10-03 07:08:25BUILDING PLAN REVIEW
 PERMIT: 08090396
 ADD: 8190 OKEECHOBEE BLVD.
 CONT:?
 TEL: (561)478-7477
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 NOTE: A CHANGE OF OCCUPANCY SHALL MEET THE REQUIREMENTS
 OF THE FBC (EXISTING) CH. 8.
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE DRAWINGS.
  
 3) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 4) 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS.
  
 61G15-23.002(2) FL. ADMIN. CODE. EACH SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S, SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. A
 TITLE BLOCK SHALL BE USED ON EACH SHEET CONTAINING THE
 PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER.
  
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6) PLEASE INDICATE THE TYPE OF BUILDING PER CHAPTER 6
 AND TABLE 601. THE USE AND OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 3 SHALL ALSO BE STATED ON THE PLANS. FBC 1004
 THE OCCUPANT LOAD OF THE SPACE SHALL BE STATED ON THE
 DRAWINGS. SHOW THE OCCUPANT LOAD OF EACH ROOM ON THE
 PLANS. PLEASE INDICATE IF THE BUILDING IS EQUIPPED WITH
 A FIRE SPRINKLER SYSTEM.
  
 7) PROVIDE AN EXISTING FLOOR PLAN AND PROPOSED FLOOR
 PLAN SHOWING ALL THE CHANGES TO THE LAYOUT OF THE
 STRUCTURE. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 8) PER TABLE 302.3.2 FIRE PARTITIONS SEPARATING A
 BUSINESS OCCUPANCY AND A DAYCARE OCCUPANCY SHALL HAVE A
 2 HOUR RATING; PROVIDE THE UL ASSEMBLY FOR THE WALL.
 FBC (EXISTING) 812.1.2 DUE TO THE FACT THAT THIS IS A
 CHANGE OF OCCUPANCY WITH A SEPARATION WALL, THE
 SEPARATED WALL SHALL MEET THE REQUIREMENTS OF FBC
 CHAPTER 7
  
 9) SUBMIT A LIFE SAFETY PLANS SHOWING THE MEANS OF
 EGRESS WHICH SHALL INCLUDE THE EXIT ACCESS FBC 1013,
 THE EXIT FBC 1017 AND THE EXIT DISCHARGE FBC 1023.
 INDICATE THE EARLY WARNING SYSTEM, SMOKE CONTROL SYSTEM
 ETC.
  
 10) FBC 1008.1.2 DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 MORE.
  
 11) SHOW THE ACCESSIBLE ROUTE TO THE BUILDING
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING
 WITH 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) THE CORRIDORS SHALL BE FIRE-RESISTANCE RATED IN
 ACCORDANCE WITH TABLE 1016.1 PLEASE INDICATE THE WIDTH
 OF EACH CORRIDOR ON THE PLANS PER 1016.2.
 14) THE PLANS SUBMITTED ARE MISSING SOME ROOM AND DOOR
 DIMENSIONS WHICH ARE IMPORTANT FOR THE REVIEW. DETAIL
 ELEVATION DRAWINGS FOR THE SINK IN THE TODDLER ROOM ARE
 MISSING FROM THE DRAWINGS. WILL THE KITCHEN BE USED TO
 PREPARE MEALS FOR THE KIDS? IF SO, PROVIDE INFORMATION
 ON THE SUPPRESSION SYSTEM FOR THE KITCHEN IN
 CONFORMANCE WIT 904.2.1 ADDITIONAL INFORMATION IS
 REQUIRED 106.1.2*
  
 NOTE: ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW
 WHEN A FULL SET OF ARCHITECTURAL PLANS ARE SUBMITTED. A
 GENERAL CONTRACTOR SHALL BE SIGNED ON THE APPLICATION
 TO DO THE WORK AT THIS PROJECT. A FAIR MARKET VALUE
 SHALL BE INDICATED ON THE PERMIT APPLICATION WHICH
 SHALL INCLUDE, STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, ARCHITECTURAL DESIGN FEES,
 MARKETING COSTS, AND OVERHEAD AND PROFIT EXCLUDING
 LAND. 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved