Plan Review Notes
Plan Review Notes For Permit 08090396
Permit Number 08090396
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-07 11:58:52PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A PERMIT APPLICATION WAS NOT WITH THE SUBMITTAL. ANY
 OWNER, AUTHORIZED AGENT, OR CONTRACTOR WHO INTENDES TO
 CONSTRUCT ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR
 CHANGE THE OCCUPANCY OF A BUILDING STRUCTURE, SHALL
 FIRST MAKE APPLICATION TO THE BUILDING OFFICIAL AND
 OPTAIN THE REQUIRED PERMIT. PER FBC-2004 CHAPTER 1,
 (W.P.B. AS AMENDED) SECTION 105.1 REQUIRED.
  
 2. DECLARE THE GOVERNING CODE ON THE PLANS (FBC-2004
 WITH 2007 REVISIONS). PER FBC-2004 CHAPTER 1, (W.P.B.
 AS AMENDED) SECTION 106.5 RETENTION OF CONSTRUCTION
 DOCUMENTS.
  
 3. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 4. THE PLAN SUBMITTED DOES NOT CONTAIN ENOUGH
 INFORMATION TO DO A PROPER PLUMBING PLAN REVIEW. PLEASE
 PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN CLEARLY INDICATING ALL PROPOSED CHANGES TO THE
 STRUCTURE. PLEASE KNOW THAT IF THERE IS NEW PROPOSED
 PLUMBING FOR THE STRUCTURE THAT SANITARY AND POTABLE
 WATER RISER DIAGRAMS ARE REQUIRED. PER FBC-2004 CHAPTER
 1, (W.P.B. AS AMENDED) SECTION 106.3.1.3 PLUMBING (3),
 (4), (8), (10), (11), (12), (13).
  
 5. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY OF THE GROUP LISTED BELOW.
 DAY CARE (SEE SECTION 313): GROUP D
  
 6. PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES FOR OCCUPANCY GROUP D, ARE
 PER THE FOLLOWING.
  
 A} WATER CLOSETS MALE/FEMALE= 1 PER 50.
  
 B} LAVATORIES MALE/FEMALE= 1 PER 50.
  
 C} DRINKING FOUNTAIN= 1 PER 100.
  
 D} 1 SERVICE SINK.
  
 E} (D) FOR DAY CARE NURSERIES, A MAXIMUM OF ONE BATHTUB
 SHALL BE REQUIRED.
  
 NOTE: PLEASE KNOW THAT THE SUBMITTED FLOOR PLAN DOES
 NOT CLEARLY INDICATE THE REQUIRED DRINKING FOUNTAIN AND
 BATHTUB. PLEASE KNOW THAT ALL PLUMBING FIXTURES SHALL
 BE ACCESSIBLE PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION THE
 FOLLOWING SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28.
 11-4.16.3 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 7. PLAN SHEET IS INDICATING A KITCHEN: PLEASE KNOW THAT
 A GREASE INTERCEPTOR MAY BE REQUIREDTO RECIEVE THE
 DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN
 WASTE LOCATED IN FOOD PREPERATION AREAS. THE MINIMUM
 SIZE GREASE INTERCEPTOR REQUIRED IS 750 GAL. PER
 MUNICIPAL CODE ARTICLE III SECTION 90-124, THE
 EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND
 LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT HOLLY MCGRATH
 (LABORATORY SUPERVISOR) HER PHONE NUMBER IS (561)
 822-2200 EXT. 2271, HER E-MAIL ADDRESS IS
 [email protected] AND HER FAX NUMBER IS (561) 822-2279.
 NOTE: WRITTEN APPROVAL IS REQUIRED OF THE
 EXISTING/PROPOSED GREASE INTERCEPTOR OR DOCUMENTATION
 THAT A GREASE INTERCEPTOR IS NOT REQUIRED FROM
 ENVIRONMENTAL COMPLIANCE BEFORE A PERMIT CAN BE ISSUED.
  
 8. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **PLEASE KNOW THAT ADDITIONAL COMMENTS MAY APPEAR ON
 THE NEXT REVIEW WHEN A COMPLETE SET OF ARCHITECTURAL
 PLANS ARE SUBMITTED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved