2008-10-03 13:54:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 CHANGE OF OCCUPANCY
 *** DENIED ***
  
 1) PLAN SUBMITTED DOES NOT CONTAIN ENOUGH INFORMATION
 TO DO A PROPER PLAN REVIEW. PLEASE SUBMIT A MECHANICAL
 PLAN THAT SHOWS THE A/C DUCT SYSTEM WITH EXISTING OR
 NEW FIRE DAMPERS IN ALL REQUIRED DUCTS AND AIR TRANSFER
 OPENINGS THAN PENETRATE RATED WALLS FOR SEPARATION OF
 MIXED OCCUPANCIES AND RATED CORRIDORS, PER 2004 FBC/EB
 812.1.2, FBC TABLE 302.3.2 AND FBC/M 607.
  
 2) SHOW ON MECHANICAL PLAN THE OUTDOOR AIR CALCULATIONS
 SO IT MAY BE ADJUSTED FOR THIS OCCUPANCY, PER 2004
 FBC/EB 809.1 AND FBC/M 401.3 AND 403.3.
  