| Date |
Text |
| 2008-10-03 16:09:16 | ***DENIED*** |
| | |
| | 1) SEE BUILDING COMMENTS #3 AND #4 FOR FS AND FAC |
| | REQUIREMENTS FOR PLAN SUBMITTAL. |
| | |
| | 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE |
| | SAFETY SHALL COMPLY WITH NFPA 101, 2003. ADD NOTE TO |
| | PLANS |
| | |
| | 3) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY |
| | WITH NFPA 241. ADD NOTE TO PLANS |
| | |
| | 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR |
| | WALLS AND CEILING SPECIFIC TO THIS PROJECT. |
| | |
| | 5) IS BUILDING CURRENTLY PROTECTED BY AN AUTOMATIC FIRE |
| | SPRINKLER SYSTEM? |
| | |
| | 6) FIRE ALARM SYSTEM IN ACCORDANCE WITH 101, SEC. 9.6 |
| | IS REQUIRED. ADDITIONALLY, SEPARATE SHOP DRAWINGS AND |
| | PERMIT REQUIRED PRIOR TO INSTALLATION. |
| | |
| | 7) PROVIDE LIFE SAFETY SHEET ILLUSTRATING REQUIRED |
| | MEANS OF EGRESS AND MAXIMUM TRAVEL DISTANCE |
| | INFORMATION. |
| | |
| | 8) PROVIDE OCCUPANT LOAD INFORMATION. |
| | |
| | 9) ILLUSTRATE THE LOCATIONS OF ALL ILLUMINATED EXIT |
| | SIGNS AND EMERGENCY LIGHTING FACILITIES. |
| | |
| | 10) EVERY ROOM OR SPACE SHALL BE PROVIDED WITH A RESCUE |
| | WINDOW UNLESS BUILDING IS PROTECTED BY AN AUTOMATIC |
| | FIRE SPRINKLER SYSTEM, OR THE ROOM OR SPACE DOOR LEADS |
| | DIRECTLY TO THE OUTSIDE. |
| | |
| | 11) EMERGENCY PLANS IN ACCORDANCE WITH 101, SEC 4.8 |
| | SHALL BE PROVIDED AND SHALL BE FORWARDED TO THE BUREAU |
| | OF FIRE PREVENTION FOR REVIEW AND APPROVAL. (561) |
| | 804-4724 |
| | |
| | 12) ANY DOOR IN A REQUIRED MEANS OF EGRESS SERVING AN |
| | AREA OF 100 OR GREATER OCCUPANTS SHALL BE PROVIDED WITH |
| | PANIC OR FIRE EXIT HARDWARE. |
| | |
| | 13) BATHROOM DOORS SHALL BE DESIGNED TO BE OPENED FROM |
| | THE OUTSIDE BY STAFF. |
| | |
| | 14) PLANS SHOW A KITCHEN. PROVIDE INFORMATION AS TO THE |
| | USE OF THAT AREA REGARDING COOKING. FOODS THAT PRODUCE |
| | GREASE LADEN VAPORS SHALL BE COOKED UNDER APPROVED |
| | HOOD/SUPPRESSION PROTECTED EQUIPMENT. |
| | |
| | |
| | MIKE WENNERGREN, ASST. FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |