| Plan Review Notes For Permit 08090384 |
| Permit Number |
08090384 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-24 16:51:12 | | | | | | | | | | | | | PASSED/PROVISO | | | SHT M-2 REVISION REQUIRED. THE VENT UPSTREAM OF THE P-6 | | | MOP SINK IS A HORIZONTAL DRY VENT WHICH IS NOT | | | APPROVED. THE P-1 W/C IN THE WOMEN'S ACCESSIBLE STALL | | | IS NOT VENTED AND DOES NOT REFLECT THE FLOOR PLAN. THE | | | FLOOR DRAIN ON THE SANT. RISER DIAGRAM DOES NOT REFLECT | | | THE FLOOR PLAN. THE FLOOR PLAN SHOWS THE CONNECTION | | | UPSTREAM OF THE SECOND P-2 WATER CLOSET BUT IS SHOWN | | | DOWNSTREAM OF THE 1ST P-2 W/C. PLEASE CORRELATE. SUBMIT | | | REVISION AS SOON AS POSSIBLE SO AS NOT TO HOLD UP | | | INSPECTIONS. | | | | | | | | | | | | | | | . |
|