| 2008-12-01 11:06:36 | BUILDING PLAN REVIEW |
| | PERMIT: 08090382 |
| | ADD: 150 CLEARWATER DRIVE |
| | CONT: CATALFUMO |
| | TEL: (561)694-8853 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | BUS SHELTER# 6 |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) COMPLIED, COUNTY PROJECT NOC NOT REQUIRED. |
| | |
| | 1C) 2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS SHEET S-3 |
| | NEEDS TO UPDATE SUPPLEMENTS OF THE 2007SUPPLEMENTS. |
| | RESPONSE SHEET INDICATES THAT SHEET S-3 NEEDS TO UPDATE |
| | SUPPLEMENTS OF THE 2007 SUPPLEMENTS, BUT THERE IS NO |
| | S-3 IN THE PACKAGE. |
| | |
| | 1D) THE PERMIT APPLICATION UNDER ADDRESS IS INDICATED |
| | AS 150 CLEARWATER DRIVE, THIS IS A SITE ADDRESS AND |
| | WILL REQUIRE A SEPERATE ADDRESS FOR THE RESTROOMS. |
| | PLEASE CONTACT JAMES JUDGE AT (561)822-1226, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 1E) 2ND REQUEST, PLEASE CONSOLIDATE PLANS INTO TWO |
| | SEPERATE STAPLED SETS OF PLANS. THE PERMIT APPLICATION |
| | INDICATES A BUS SHELTER TO BE CONSTRUCTED. PLANS |
| | SUBMITTED ARE TWO SETS OF A6 & A7 AND SEVEN 2OF 65 |
| | CIVIL DRAWINGS. SINCE THIS WAS NOT SUBMITTED AS A |
| | MASTER PLAN, EACH INDIVIDUAL PERMIT APPLICATION WILL |
| | NEED TO SUBMIT 2 SETS OF ALL DOCUMENTS. PLEASE PROVIDE |
| | THE REQUIED (2) SETS OF PLANS WITHIN THIS PERMIT |
| | APPLICATION FOR COMPLIANCE WITH MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS 106.3.5.1.1. |
| | SITE PLAN |
| | OCCUPANCY GROUP REQUIREMENTS SHALL BE DETERMINED |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED PLEASE |
| | PROVIDE THE MINIMUM BUILDING TYPE CONSTRUCTION. TABLE |
| | 503/ TABLE 601 |
| | SOILS CONDITION |
| | BUILDING ENVELOPE COMPONENTS |
| | WIND DESIGN CRITERIA, STRUCTURAL NOTES LOCATED ON SHEET |
| | A3 ARE INDICATED ON SHEET A6 BUT NOT INCLUDED. |
| | |
| | 1F) AS OF 9-29-08 PERMIT FEE S HAVE NOT BEEN PAID, FEES |
| | ARE TO BE PAID AT TIME OF PERMIT APPLICATION. FEES OWED |
| | ARE $780.52,. CITY CODE OF ORDINANCES18.1(D) ALL PERMIT |
| | FEES MUST BE PAID IN FULL AT TIME OF PERMIT |
| | APPLICATION. |
| | |
| | 1G) NEW COMMENT: THE PERMIT APPLICATION UNDER PARCEL |
| | ID# HAS THE INCORRECT PROPERTY CONTROL NUMBER THE |
| | CORRECT PCN IS 74-43-43-21-27-001-0000, PLEASE CORRECT. |
| | |
| | 2) SECOND REQUEST, PLEAS E SUBMIT 2 ORIGINALS SIGNED |
| | AND SEALED SOILS REPORTS. 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR OF |
| | PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 3A) GLASS WIND BREAK -FOR WIND, LARGE MISSILE TESTING |
| | NOT REQUIED RULE 9B-72 (31) (B), WILL REQUIRE WIND LOAD |
| | CALCS FOR GLAZING. 1609.6.RESPONSE SHEET INDICATES LOAD |
| | CALCULATIONS ARE ATTACHED TO SHEET A-7, THESE ARE THE |
| | WIND PRESSURES NOT THE LOAD CALCULATIONS. |
| | |
| | 3B-5)COMPLIED. |
| | |
| | 6) 2ND REQUEST, PLANS DO NOT PROVIDE INFORMATION ON |
| | TERMITE TREATMENT AS PER SECTION 1816.1, OR FOR A VAPOR |
| | BARRIER AS REQUIRED IN 1816.1.4. PLEASE SEE ATTACHED |
| | INFORMAL INTERRPRETATIONS FROM BOAF WEBSITE. PLEASE SEE |
| | PERMIT# 08090377. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |