| Plan Review Notes For Permit 08090377 |
| Permit Number |
08090377 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-03-31 11:32:11 | ** DENIED REVIEW ** | | | | | | 1) NOTE: SECOND SET OF PLANS NOT SEALED AS REQUIRED PER | | | FS 471.025, FAC 61G15-23.002 | | | CALLED ENGINEER AND LEFT MESSAGE TO COME IN AND SEAL | | | PLANS. REVIEW TO REMIAN IN FAILED STATUS UNTIL PLANS | | | ARE SEALED. THIS SET OF PLANS WILL NOT BE RELEASED. | | | | | | ** REDLINED PLANS ONE SE-3, THE NEW LOW VOLTAGE CAMERAS | | | ARE NOT INCLUDED. A SEPARATE PERMIT FOR LV CAMERAS IS | | | REQUIRED FOR EACH. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|