| 2008-09-19 10:38:16 | BUILDING PLAN REVIEW |
| | PERMIT: 08090375 |
| | ADD: 307 EVERNIA AVE |
| | CONT: RAYMOND H. NORDINE |
| | TEL: (561)655-1912 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 9-19-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) INDICATE THE OCCUPANT LOAD OF EACH NEW CONFERENCE |
| | ROOM AND THE TOTAL OCCUPANCY OF THE SPACE PER TABLE |
| | 1004.1.2. |
| | |
| | 3) IF THIS BUILDING HAS A SPRINKLER SYSTEM, PLEASE |
| | STATE THIS INFORMATION ON THE PLANS. NOW THE SPACE IS |
| | ALTERED SHOW THE LAYOUT AND LOCATION OF THE SPRINKLER |
| | HEADS IN RELATION TO THE NEW ROOMS; THIS INFORMATION |
| | CAN BE SHOW ON THE CEILING PLANS WHICH IS ALSO MISSING |
| | FROM THE DRAWINGS. FBC 106.3.5.1.1(5) FS 553.79(2). |
| | |
| | 4) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. INDICATE THE INTERIOR |
| | FINISHES ON THE PLANS. |
| | |
| | 5) WALL TYPES W-1 AND W-2 FAIL TO INDICATE HOW THE TOP |
| | AND BOTTOM TRACK WILL BE FASTEN TO THE RESPECTIVE |
| | STRUCTURE. STATE THE TYPE OF FASTENERS TO BE USED TO |
| | HOLD THE TRACK IN PLACE AND THE SPACING OF THE |
| | FASTENERS. ADDITIONAL INFORMATION REQUIRED 106.1.2 |
| | |
| | 6) THE CLAIMED VALUATION THE PERMIT APPLICATION IS LOW. |
| | FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING |
| | LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD) |
| | MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER FBC |
| | 108.3*. |
| | |
| | 7) FBC 11-7(2) (I) A PORTION OF THE RECEPTIONIST |
| | COUNTER SHALL MAXIMUM HEIGHT OF 36 INCHES AND MINIMUM |
| | WIDTH OF 36 INCHES. PLEASE SHOW THIS INFORMATION ON THE |
| | SUBMITTED DRAWINGS. THE WALLS AROUND THE RECEPTIONIST |
| | SHOW A 42 INCH HIGH WALL. |
| | |
| | 8) INDICATE THE TYPE AND HEIGHT OF THE BUILDING PER FBC |
| | TABLE 601 AND TABLE 503. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |