| 2009-03-24 16:20:37 | ** PLANS DENIED ** |
| | SOME OF THE SAME NOTES FROM THE PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: THIS IS A REPEAT REQUEST TO SUBMIT THE |
| | MANUFACTURES SPECS/CUT SHEETS FOR THE NEW PROPOSED |
| | TRANSFER SWITCH. BASED ON THE RISER THIS EQUIPMENT MUST |
| | BE SERVICE ENTRANCE RATED NOT ONLY RATED AS SERVICE |
| | EQUIPMENT. THIS EQUIPMENT MUST HAVE OVER CURRENT |
| | PROTECTION AND BE MUST ALSO BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. |
| | THERE SEEMS TO BE SOME SORT OF MISPRINT WITH THE RATING |
| | OF THE EQUIPMENT ALSO. SHOWN AS 1001. |
| | 230.70, 230.71, 230.76, 230.79, 110.9, 110.3, 90.7 |
| | |
| | 2) NOTE: PLEASE SEE THE INPUT DATA REPORT FOR LIGHTING |
| | FOR EXTERIOR. WHEN USING LIGHTING PER HEALTH, SAFETY |
| | STATUTES, ORDINANCE, OR REGULATION THIS WILL EXEMPT THE |
| | LIGHTING AND REMOVE IT FROM THE OVER ALL FIGURE. AS |
| | THERE IS NO ORDINANCE, STATUTE OR OTHER REGULATIONS |
| | WHICH REQUIRES THIS LIGHTING, THIS USE MAY NOT BE USED. |
| | PLEASE ADJUST CALCULATIONS. |
| | 13-415.2, 13-415.2.ABC.1.3. |
| | LIGHTING IN A RETAIL OCCUPANCY SPECIFIC TO DISPLAY |
| | AREAS HAS AN ADDITIONAL ALLOWANCE UNDER THE 2004 FBC |
| | HOWEVER IT IS SPECIFIC TO THE SQUARE FOOTAGE OF THE |
| | DISPLAY AREA. |
| | |
| | 3) NOTE: PLEASE SEE NOTES MARKED AS *IMPORTANT* ON THE |
| | PREVIOUS REVIEW. PLEASE BE SURE TO REMOVE THE OLD |
| | VOIDED SHEETS FROM SETS AND INSERT THE NEW REVISED |
| | SHEETS INTO SETS FOR REVIEW AND STAMPING. |
| | |
| | 4) NOTE: PLEASE SEE THE NEW REVISED SHEETS WHICH WERE |
| | SUBMITTED ARE NOT SIGNED, DATED OR SEALED BY THE |
| | DESIGNER OF RECORD. FS 481.221 |
| | |
| | 5) NOTE: PLEASE SEE RISER AS THIS STILL INDICATES AN |
| | EQUIPMENT GROUNDING CONDUCTOR FROM THE GUTTER TO THE |
| | NEW TRANSFER SWITCH. PER 250.6, 250.24 THERE CAN NOT BE |
| | ANY EQUIPMENT GROUNDING CONDUCTORS BEFORE THE FIRST |
| | MEANS OF DISCONNECT ON A SERVICE. ONLY AFTER THE FIRST |
| | MEANS OF DISCONNECT IS EQUIPMENT GROUNDING CONDUCTORS |
| | INSTALLED. |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |