Plan Review Notes
Plan Review Notes For Permit 08090363
Permit Number 08090363
Review Stop E
Sequence Number 3
Notes
Date Text
2009-03-24 16:20:37** PLANS DENIED **
 SOME OF THE SAME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: THIS IS A REPEAT REQUEST TO SUBMIT THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE NEW PROPOSED
 TRANSFER SWITCH. BASED ON THE RISER THIS EQUIPMENT MUST
 BE SERVICE ENTRANCE RATED NOT ONLY RATED AS SERVICE
 EQUIPMENT. THIS EQUIPMENT MUST HAVE OVER CURRENT
 PROTECTION AND BE MUST ALSO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
 THERE SEEMS TO BE SOME SORT OF MISPRINT WITH THE RATING
 OF THE EQUIPMENT ALSO. SHOWN AS 1001.
 230.70, 230.71, 230.76, 230.79, 110.9, 110.3, 90.7
  
 2) NOTE: PLEASE SEE THE INPUT DATA REPORT FOR LIGHTING
 FOR EXTERIOR. WHEN USING LIGHTING PER HEALTH, SAFETY
 STATUTES, ORDINANCE, OR REGULATION THIS WILL EXEMPT THE
 LIGHTING AND REMOVE IT FROM THE OVER ALL FIGURE. AS
 THERE IS NO ORDINANCE, STATUTE OR OTHER REGULATIONS
 WHICH REQUIRES THIS LIGHTING, THIS USE MAY NOT BE USED.
 PLEASE ADJUST CALCULATIONS.
 13-415.2, 13-415.2.ABC.1.3.
 LIGHTING IN A RETAIL OCCUPANCY SPECIFIC TO DISPLAY
 AREAS HAS AN ADDITIONAL ALLOWANCE UNDER THE 2004 FBC
 HOWEVER IT IS SPECIFIC TO THE SQUARE FOOTAGE OF THE
 DISPLAY AREA.
  
 3) NOTE: PLEASE SEE NOTES MARKED AS *IMPORTANT* ON THE
 PREVIOUS REVIEW. PLEASE BE SURE TO REMOVE THE OLD
 VOIDED SHEETS FROM SETS AND INSERT THE NEW REVISED
 SHEETS INTO SETS FOR REVIEW AND STAMPING.
  
 4) NOTE: PLEASE SEE THE NEW REVISED SHEETS WHICH WERE
 SUBMITTED ARE NOT SIGNED, DATED OR SEALED BY THE
 DESIGNER OF RECORD. FS 481.221
  
 5) NOTE: PLEASE SEE RISER AS THIS STILL INDICATES AN
 EQUIPMENT GROUNDING CONDUCTOR FROM THE GUTTER TO THE
 NEW TRANSFER SWITCH. PER 250.6, 250.24 THERE CAN NOT BE
 ANY EQUIPMENT GROUNDING CONDUCTORS BEFORE THE FIRST
 MEANS OF DISCONNECT ON A SERVICE. ONLY AFTER THE FIRST
 MEANS OF DISCONNECT IS EQUIPMENT GROUNDING CONDUCTORS
 INSTALLED.
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved