| 2009-02-01 10:50:02 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY: |
| | |
| | 1. *PREVIOUS COMMENT* PAGE M-1 FLOOR PLAN SHOWS DUCT |
| | SMOKE DETECTORS ON THE RETURN SIDE OF AHU 1 AND AHU 2. |
| | DUCT DETECTORS SHALL BE ON THE SUPPLY SIDE OF THE FANS |
| | IN ACCORDANCE WITH FBCM 606.2.1. |
| | |
| | *COMMENT #1 PARTIALLY ADDRESSED*: SOMKE DETECTORS HAVE |
| | BEEN RELOACTED TO SUPPLY SIDE OF THE SYSTEM AS REQUIRED |
| | BY FBCM 606.2.1. HOWEVER, THE DETECTOR FOR AHU 1 IS |
| | SHOWN DOWNSTREAM OF THE FIRST AND LARGEST SUPPLY |
| | BRANCH. SMOKE DETECTORS SHALL BE INSTALLED IN A |
| | LOCATION WHERE THEY WILL MONITOR THE ENTIRE AIRFLOW |
| | CONVEYED BY THE SYSTEM IN ACCORDANCE WITH FBCM 606.3. |
| | IN OTHER WORDS, THE DETECTOR MUST BE LOCATED BEFORE OR |
| | UPSTREAM OF THE FIRST SUPPLY BRANCH. SHOW THIS DETECTOR |
| | ON PLANS IN A LOCATION WHICH IS IN COMPLIANCE WITH THIS |
| | FBCM 606.2.1 AND 606.3. PLEASE SHOW COMPLIANCE ON |
| | PLANS, DO NOT JUST QUOTE THE CODE SECTION IN ACCORDANCE |
| | WITH FBCB 106.1.1. |
| | |
| | 2. *PREVIOUS COMMENT* OUTSIDE AIR INTAKES FOR AHU-1 AND |
| | AHU-2 SHALL BE PROVIDED WITH SHUTOFF DAMPER CONTROLS IN |
| | ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. |
| | |
| | *COMMENT #2 PARTIALLY ADDRESSED*: ARE MOTORIZED OR |
| | MANUAL BACKDRAFT DAMPERS TO BE INSTALLED AT THIS |
| | LOCATION? IF A MOTORIZED DAMPER IS TO BE USED, |
| | PROVISIONS FOR POWER AND CONTROL WILL BE REQUIRED. |
| | PLEASE SHOW ON PLANS HOW COMPLIANCE WITH FBCB |
| | 13-407.1.ABC.3.3 IS TO BE ACHIEVED RATHER THAN QUOTING |
| | THE SECTION PER FBCB 106.1.1. |
| | |
| | 3. OK |
| | |
| | 4. OK |
| | |
| | 5. *PREVIOUS COMMENT* NO INSTALLATION DETAILS PROVIDED |
| | IN PLANS. PROVIDE DETAILED INSTALLATION INSTRUCTIONS |
| | FOR ALL MECHANICAL EQUIPMENT AND APPLIANCES WHICH ARE |
| | TO BE INSTALLED OUTDOORS. ALSO INCLUDE SUPPORTING |
| | DOCUMENTATION FOR WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH FBCM 301.13. ALSO |
| | REQUIRED IS DATA FROM ALL OUTDOOR APPLIANCE |
| | MANUFACTURERS SHOWING THEIR APPLIANCES ARE DESIGNED AND |
| | CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE WITH |
| | THIS SECTION. THIS INCLUDES ALL CONDENSING UNITS AND |
| | HOOD EXHAUST/MAKE-UP AIR FANS. |
| | |
| | *COMMENT ADDRESSED*: HOWEVER, WIND RESISTANCE |
| | REQUIREMENTS FOR ALL OUTDOOR APPLIANCES AND EQUIPMENT |
| | NOT COVERED BY THIS PERMIT MUST BE DEMONSTRATED AT TIME |
| | OF SEPARATE PERMIT APPLICATION SUCH AS THE KITCHEN |
| | EXHAUST FAN, MAKEUP AIR FAN, REMOTE CONDENSERS FOR |
| | WALK-IN COOLERS. |
| | |
| | 6. OK. SUBMIT SEPARAT PERMIT APPLICATIONS WITH FULL |
| | DOCUMENTATION FOR THE KITCHEN HOOD AND VENTILATION |
| | EQUIPMENT. ALSO, A SEPARATE PERMIT APPLICATION IS |
| | REQUIRED FOR THE KITCHEN HOOD FIRE SUPPRESSION SYSTEM. |
| | |
| | 7. OK SUBJECT TO FIELD INSPECTOR'S VERIFICATION. |
| | |
| | 8. OK |
| | NOTE: MECHANICAL ONLY REVIEWS FOR MECHANICAL PORTIONS |
| | OF THE ENERGY CALCULATIONS. PLEASE SEE OTHER TRADE |
| | REVIEWS FOR POSSIBLE ADDITIONAL ENERGY CODE RELATED |
| | COMMENTS. |
| | |