2009-02-01 10:50:02REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY:
  
 1. *PREVIOUS COMMENT* PAGE M-1 FLOOR PLAN SHOWS DUCT
 SMOKE DETECTORS ON THE RETURN SIDE OF AHU 1 AND AHU 2.
 DUCT DETECTORS SHALL BE ON THE SUPPLY SIDE OF THE FANS
 IN ACCORDANCE WITH FBCM 606.2.1.
  
 *COMMENT #1 PARTIALLY ADDRESSED*: SOMKE DETECTORS HAVE
 BEEN RELOACTED TO SUPPLY SIDE OF THE SYSTEM AS REQUIRED
 BY FBCM 606.2.1. HOWEVER, THE DETECTOR FOR AHU 1 IS
 SHOWN DOWNSTREAM OF THE FIRST AND LARGEST SUPPLY
 BRANCH. SMOKE DETECTORS SHALL BE INSTALLED IN A
 LOCATION WHERE THEY WILL MONITOR THE ENTIRE AIRFLOW
 CONVEYED BY THE SYSTEM IN ACCORDANCE WITH FBCM 606.3.
 IN OTHER WORDS, THE DETECTOR MUST BE LOCATED BEFORE OR
 UPSTREAM OF THE FIRST SUPPLY BRANCH. SHOW THIS DETECTOR
 ON PLANS IN A LOCATION WHICH IS IN COMPLIANCE WITH THIS
 FBCM 606.2.1 AND 606.3. PLEASE SHOW COMPLIANCE ON
 PLANS, DO NOT JUST QUOTE THE CODE SECTION IN ACCORDANCE
 WITH FBCB 106.1.1.
  
 2. *PREVIOUS COMMENT* OUTSIDE AIR INTAKES FOR AHU-1 AND
 AHU-2 SHALL BE PROVIDED WITH SHUTOFF DAMPER CONTROLS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.3.
  
 *COMMENT #2 PARTIALLY ADDRESSED*: ARE MOTORIZED OR
 MANUAL BACKDRAFT DAMPERS TO BE INSTALLED AT THIS
 LOCATION? IF A MOTORIZED DAMPER IS TO BE USED,
 PROVISIONS FOR POWER AND CONTROL WILL BE REQUIRED.
 PLEASE SHOW ON PLANS HOW COMPLIANCE WITH FBCB
 13-407.1.ABC.3.3 IS TO BE ACHIEVED RATHER THAN QUOTING
 THE SECTION PER FBCB 106.1.1.
  
 3. OK
  
 4. OK
  
 5. *PREVIOUS COMMENT* NO INSTALLATION DETAILS PROVIDED
 IN PLANS. PROVIDE DETAILED INSTALLATION INSTRUCTIONS
 FOR ALL MECHANICAL EQUIPMENT AND APPLIANCES WHICH ARE
 TO BE INSTALLED OUTDOORS. ALSO INCLUDE SUPPORTING
 DOCUMENTATION FOR WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH FBCM 301.13. ALSO
 REQUIRED IS DATA FROM ALL OUTDOOR APPLIANCE
 MANUFACTURERS SHOWING THEIR APPLIANCES ARE DESIGNED AND
 CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 THIS SECTION. THIS INCLUDES ALL CONDENSING UNITS AND
 HOOD EXHAUST/MAKE-UP AIR FANS.
  
 *COMMENT ADDRESSED*: HOWEVER, WIND RESISTANCE
 REQUIREMENTS FOR ALL OUTDOOR APPLIANCES AND EQUIPMENT
 NOT COVERED BY THIS PERMIT MUST BE DEMONSTRATED AT TIME
 OF SEPARATE PERMIT APPLICATION SUCH AS THE KITCHEN
 EXHAUST FAN, MAKEUP AIR FAN, REMOTE CONDENSERS FOR
 WALK-IN COOLERS.
  
 6. OK. SUBMIT SEPARAT PERMIT APPLICATIONS WITH FULL
 DOCUMENTATION FOR THE KITCHEN HOOD AND VENTILATION
 EQUIPMENT. ALSO, A SEPARATE PERMIT APPLICATION IS
 REQUIRED FOR THE KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
  
 7. OK SUBJECT TO FIELD INSPECTOR'S VERIFICATION.
  
 8. OK
 NOTE: MECHANICAL ONLY REVIEWS FOR MECHANICAL PORTIONS
 OF THE ENERGY CALCULATIONS. PLEASE SEE OTHER TRADE
 REVIEWS FOR POSSIBLE ADDITIONAL ENERGY CODE RELATED
 COMMENTS.
  