Plan Review Notes
Plan Review Notes For Permit 08090363
Permit Number 08090363
Review Stop E
Sequence Number 2
Notes
Date Text
2009-01-05 15:33:01** DENIED 2ND REVIEW **
  
  
 **SEE NEW NOTES BELOW DUE TO REVISED RISER WHICH DID
 NOT CONTAIN SOME OF THESE ITEMS ON PREVIOUS REVIEWED
 PLANS.
  
  
  
 1) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 ON THE NEW PROPOSED SERVICE ENTRANCE RATE TRANSFER
 SWITCH.
 110.3,90.7, ETC
  
 2) NOTE: RISER NOW HAS BEEN REVISED TO INDICATE A #4
 NEUTRAL AS PART OF THE FEEDERS FROM PANEL *A* TO NEW
 SUB PANEL *D*. THIS MUST BE A MISPRINT FOR EQUIPMENT
 GROUNDING CONDUCTOR?
 250
 FBC 106.1.1, FOR CLARITY AND COORDINATION OF PLANS.
  
 3) NOTE: PLEASE ADJUST RISER WITH NEW CONDUCTORS NOW
 BEING SHOWN FROM GUTTER TO THE NE W TRANSFER SWITCH.
 THE NOTES ABOVE REQUEST THE SPECS/CUT SHEETS HOWEVER
 THE RISER INDICATES THE OLD DISCONNECT *C* BEING FED
 FROM TWO LOCATIONS.
 THE RISER ALSO INDICATES AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THE GUTTER TO THE TRANSFER SWITCH WHICH
 IS NOT PERMITTED.250.6,250.24.
 * EQUIPMENT GROUNDING CONDUCTORS* ARE ONLY INSTALLED
 AFTER THE FIRS MEANS OF DISCONNECT.
  
 4) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO
 THE FLA COM ENERGY CALCULATIONS SUBMITTED. PART OF THE
 COMMENT IS THE FACT ALL THE INFORMATION ON PLANS NEEDS
 TO COORDINATE WITH THE SUBMITTED INPUT DATA REPORT.
 THIS IS NOT COMPLIANT.
 ONE EXAMPLE: THERE ARE MORE FIXTURES ON THE PLANS FOR
 THE INTERIOR LIGHTING THAN SHOWN ON THE IDR SUBMITTED.
 PLEASE SEE TYPE D, G ETC.
 PLEASE SEE ELECTRICAL PLANS WHICH ALSO CONTAIN A LIGHT
 FIXTURE SYMBOL HOWEVER NO DESIGNATION IS NOTED ALONG
 WITH NO CIRCUITING.
 PLEASE SEE 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE COORDINATE ALL.
 THIS IS NOT THE ONLY ITEM.
 PLEASE SEE THE SUBMITTED SHEET 4 OF 8 WHICH IDENTIFIES
 THE BUILDING END USES. WHERE DOES THE DESIGN OF 358.30
 AND THE REFERENCE OF 390.30 COME FROM.
 THIS IS NOT LIKE ANY OTHER CALCULATIONS EVER SUBMITTED.
 THE REFERENCE HAS ALWAYS BEEN 100 AND THE DESIGN IS
 DOWN FROM THERE.
 13-101, 13-400.3.A.
 PLEASE SEE 13-401- 13-412 FOR OTHERS.
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  