| 2009-01-05 15:33:01 | ** DENIED 2ND REVIEW ** |
| | |
| | |
| | **SEE NEW NOTES BELOW DUE TO REVISED RISER WHICH DID |
| | NOT CONTAIN SOME OF THESE ITEMS ON PREVIOUS REVIEWED |
| | PLANS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | ON THE NEW PROPOSED SERVICE ENTRANCE RATE TRANSFER |
| | SWITCH. |
| | 110.3,90.7, ETC |
| | |
| | 2) NOTE: RISER NOW HAS BEEN REVISED TO INDICATE A #4 |
| | NEUTRAL AS PART OF THE FEEDERS FROM PANEL *A* TO NEW |
| | SUB PANEL *D*. THIS MUST BE A MISPRINT FOR EQUIPMENT |
| | GROUNDING CONDUCTOR? |
| | 250 |
| | FBC 106.1.1, FOR CLARITY AND COORDINATION OF PLANS. |
| | |
| | 3) NOTE: PLEASE ADJUST RISER WITH NEW CONDUCTORS NOW |
| | BEING SHOWN FROM GUTTER TO THE NE W TRANSFER SWITCH. |
| | THE NOTES ABOVE REQUEST THE SPECS/CUT SHEETS HOWEVER |
| | THE RISER INDICATES THE OLD DISCONNECT *C* BEING FED |
| | FROM TWO LOCATIONS. |
| | THE RISER ALSO INDICATES AN EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE GUTTER TO THE TRANSFER SWITCH WHICH |
| | IS NOT PERMITTED.250.6,250.24. |
| | * EQUIPMENT GROUNDING CONDUCTORS* ARE ONLY INSTALLED |
| | AFTER THE FIRS MEANS OF DISCONNECT. |
| | |
| | 4) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO |
| | THE FLA COM ENERGY CALCULATIONS SUBMITTED. PART OF THE |
| | COMMENT IS THE FACT ALL THE INFORMATION ON PLANS NEEDS |
| | TO COORDINATE WITH THE SUBMITTED INPUT DATA REPORT. |
| | THIS IS NOT COMPLIANT. |
| | ONE EXAMPLE: THERE ARE MORE FIXTURES ON THE PLANS FOR |
| | THE INTERIOR LIGHTING THAN SHOWN ON THE IDR SUBMITTED. |
| | PLEASE SEE TYPE D, G ETC. |
| | PLEASE SEE ELECTRICAL PLANS WHICH ALSO CONTAIN A LIGHT |
| | FIXTURE SYMBOL HOWEVER NO DESIGNATION IS NOTED ALONG |
| | WITH NO CIRCUITING. |
| | PLEASE SEE 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE COORDINATE ALL. |
| | THIS IS NOT THE ONLY ITEM. |
| | PLEASE SEE THE SUBMITTED SHEET 4 OF 8 WHICH IDENTIFIES |
| | THE BUILDING END USES. WHERE DOES THE DESIGN OF 358.30 |
| | AND THE REFERENCE OF 390.30 COME FROM. |
| | THIS IS NOT LIKE ANY OTHER CALCULATIONS EVER SUBMITTED. |
| | THE REFERENCE HAS ALWAYS BEEN 100 AND THE DESIGN IS |
| | DOWN FROM THERE. |
| | 13-101, 13-400.3.A. |
| | PLEASE SEE 13-401- 13-412 FOR OTHERS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |