Plan Review Notes
Plan Review Notes For Permit 08090363
Permit Number 08090363
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-19 13:53:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 CITY WPB MUNICIPAL CODE
  
 1. SHT A0-1 SHOWS A NEW GREASE INTERCEPTOR. THE GREASE
 INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT,
 INDUSTRIAL PRETREATMENT DIVISION. PLEASE CONTACT MR.
 WILLIAM ROBERTS ENVIRONMENTAL COMPLIANCE AT (561)
 822-2272, FAX (561) 659-7458 OR E-MAIL
 [email protected]. ARTICLE III SECTION 90-124.
  
 2. SHT A0-1A DEMOLITION PLAN. PER SECTION 704.5 IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. ALL DEMO'D - CAPPED PIPING SHALL REMAIN
 UNCOVERED UNTIL INSPECTED BY THE FIELD INSPECTOR.
  
 3. SHT A-1 CODE STANDARDS SHALL INCLUDE THE 2007
 REVISIONS.
  
 4. SHT P-1 THE 3 COMPARTMENT SINK DETAIL SHOWS THE AIR
 GAP AS 3". PER SECTION 802.2.1 THE MINIMUM AIR GAP IS
 TWICE THE EFFECTIVE OPENING OF THE INDIRECT PIPING. THE
 INDIRECT PIPING IS INDICATED AS 2". THE MINIMUM AIR GAP
 REQUIRED IS 4".
  
 5. SHT P-2 SANITARY RISER DIAGRAM, THE FLOOR DRAIN IN
 THE TOILET ROOM IS NOT VENTED AS INDICATED. SECTION
 901.2.1. THE FLOOR DRAIN SHOULD BE CONNECTED TO THE LAV
 RISER. -- SHOW THE PIPE SIZES FOR THE TOILET FIXTURES,
 (W/C & FLOOR DRAIN). TABLES 709.1 & 710.1(1)(2).
  
 6. SHT P-2 SANITARY RISER DIAGRAM, THE PIPING TO THE
 URINAL IS AN "S" TRAP WHICH IS NOT APPROVED. SECTION
 1002.3. PLEASE SHOW THE DRAIN LINE FROM THE URINAL
 CONNECTING STRAIGHT INTO THE STACK WITHOUT THE VERTICAL
 DROP AS INDICATED ON THE RISER. (SEE RED LINE
 CORRECTION ON ONE SET OF PLANS).
  
 7. SHT P-2 SANITARY RISER DIAGRAM, CLEANOUTS ARE
 REQUIRED NEAR THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER PER SECTION 708.3.5. -- ALSO TWO WAY
 CLEANOUTS ARE REQUIRED AT THE AFFLUENT PIPING & THE
 EFFLUENT PIPING OF THE GREASE INTERCEPTOR PER UTILITY
 STANDARD FOR GREASE INTERCEPTORS.
  
 8. SHT P-2 WATER ISOMETRIC RISER DIAGRAM. A WATER
 HAMMER ARRESTOR IS REQUIRED ON THE SUPPLY PIPE FOR THE
 ICE MAKER INSTALLED NEAR THE FIXTURE IN AN EFFECTIVE
 RANGE PER PDI-HW 201. PLEASE SHOW ON RISER DIAGRAM.
 SECTION 604.9.
  
 9. SHT P-1 INDICATES GAS PIPING NOTES. A SEPARATE GAS
 PERMIT IS REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED TO BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  