| Date |
Text |
| 2008-10-06 15:20:50 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FS 526.143 AND PROVIDE BACK UP |
| | REQUIRED SYSTEM FOR MOTOR FUELING. IF A SYSTEM ALREADY |
| | EXISTS, PLEASE SHOW SYSTEM AND PROVIDE PERMITTING |
| | INFORMATION. NO CURRENT RECORDS WERE LOCATED IN OUR |
| | SYSTEM THAT THIS WORK HAS BEEN DONE. PLEASE SEE THE |
| | STATUTORY REQUIREMENT AS NOTED. |
| | |
| | 2) NOTE: PLEASE SEE FBC 13-400.3.A, .3.B, ETC AS THE |
| | VERSION SUBMITTED FOR ENERGY CALCULATIONS IS NOT |
| | ADOPTED BY THE FBC. THIS SHOULD BE VERSION 2.5. PLEASE |
| | GO TO ENERGY GAUGE WEBSITE AS THERE IS A PATCH |
| | AVAILABLE TO CHANGE TO VERSION 2.5. |
| | |
| | 3) NOTE: PLEASE SEE 13-101.1. AS THIS IS AN EXISTING |
| | BUILDING PLEASE PROVIDE HOW METHOD A IS BEING USED AS |
| | THIS WOULD BE A RENOVATION PER SECTION 202. |
| | ONLY IF ALL KNOWN COMPONENTS ARE KNOWN WOULD A METHOD A |
| | BE USED. |
| | IN EITHER CASE THE SUBMITTED CALCULATIONS ARE NOT CODE |
| | COMPLIANT. THE INPUT DATA REPORT ATTACHED AS REQUIRED |
| | IS NOT COMPLETE. |
| | FOR ONE EXAMPLE: PLEASE SEE THE IDR AS THIS SHOWS NO |
| | EXTERIOR LIGHTING. THIS SECTION OF THE IDR IS *BLANK*. |
| | HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE |
| | MANY EXTERIOR FIXTURES? |
| | PLEASE SEE FBC 13-415.2.ABC.1.3 FOR LIGHTING |
| | PERFORMANCE CALCULATIONS FOR EXTERIOR. |
| | PLEASE ALSO SEE FBC 13-415.2.ABC.1.1, .1.2 FOR INTERIOR |
| | LIGHTING. |
| | |
| | FOR EXAMPLE: THE FIXTURE WATTAGES LISTED ON THE IDR ARE |
| | NOT ALL THE SAME AS SHOWN ON THE FIXTURE LEGEND. THERE |
| | ARE SEVERAL INCONSISTENCIES. |
| | |
| | |
| | 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON ELECTRICAL PLANS AT A MINIMUM. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2004 FBC W/2007 REVISIONS. |
| | |
| | 5) NOTE: ALL LOW VOLTAGE SECURITY CAMERAS ETC WILL BE |
| | UNDER SEPARATE PERMITS WITH PLANS AND FEES. |
| | |
| | 6) NOTE: PLEASE COORDINATE ELECTRICAL RISER. AS |
| | SUBMITTED THERE ARE SEVERAL ITEMS WHICH NEED TO BE |
| | ADDRESSED. |
| | THE NEW PANEL *D* IS BEING SHOWN WITH A LOAD WHICH FAR |
| | EXCEEDS THE RATING OF THE FEEDERS AND BREAKERS SHOWN IN |
| | PANEL *A*. IN FACT PANEL *A* SHOWS ONLY A 30AMP BREAKER |
| | AND FEEDERS WHEN IN FACT PANEL *D* HAS A LOAD OF 120.5 |
| | AMPS. |
| | PLEASE ALSO SEE THE FEEDERS AS NOTED ON PANEL *D* ARE |
| | SHOWN AS 3/0 WHEN THE RISER SHOWS THESE AS 1/0. IN |
| | EITHER CASE BOTH OF THESE WOULD BE CODE COMPLIANCE |
| | BASED ON LOAD HOWEVER COORDINATION IS NEEDED WITH OVER |
| | CURRENT PROTECTION ETC. |
| | PLEASE SEE THE FEEDERS NOTED ON PANEL *A* ARE SHOWN AS |
| | 500MCM IN A 3INCH CONDUIT, YET THE RISER SHOWS THE SAME |
| | CONDUCTORS IN A 2 INCH CONDUIT. |
| | |
| | 7) NOTE: PLEASE INCLUDE NOTES FOR CONTRACTOR TO LABEL |
| | ALL MAINS FOR SERVICE PER 230.2E |
| | |
| | 8) NOTE: PLEASE SHOW ALL EQUIPMENT GROUNDING PATHS/ |
| | METHODS AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 9) NOTE: PLEASE SEE 210.8B2 AS ALL 15,20AMP 120V |
| | RECEPTACLES SERVING KITCHEN AREAS WHETHER OR NOT |
| | FEEDING APPLIANCES OR EQUIPMENT ON THE COUNTER AREAS |
| | WILL BE REQUIRED TO BE GFI OR GFI PROTECTED WITH CLASS |
| | A PROTECTION. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED OR INCOMPLETE ON PLANS THERE MAY BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT POSSIBLY |
| | BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |