 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FS 526.143 AND PROVIDE BACK UP
 REQUIRED SYSTEM FOR MOTOR FUELING. IF A SYSTEM ALREADY
 EXISTS, PLEASE SHOW SYSTEM AND PROVIDE PERMITTING
 INFORMATION. NO CURRENT RECORDS WERE LOCATED IN OUR
 SYSTEM THAT THIS WORK HAS BEEN DONE. PLEASE SEE THE
 STATUTORY REQUIREMENT AS NOTED.
  
 2) NOTE: PLEASE SEE FBC 13-400.3.A, .3.B, ETC AS THE
 VERSION SUBMITTED FOR ENERGY CALCULATIONS IS NOT
 ADOPTED BY THE FBC. THIS SHOULD BE VERSION 2.5. PLEASE
 GO TO ENERGY GAUGE WEBSITE AS THERE IS A PATCH
 AVAILABLE TO CHANGE TO VERSION 2.5.
  
 3) NOTE: PLEASE SEE 13-101.1. AS THIS IS AN EXISTING
 BUILDING PLEASE PROVIDE HOW METHOD A IS BEING USED AS
 THIS WOULD BE A RENOVATION PER SECTION 202.
 ONLY IF ALL KNOWN COMPONENTS ARE KNOWN WOULD A METHOD A
 BE USED.
 IN EITHER CASE THE SUBMITTED CALCULATIONS ARE NOT CODE
 COMPLIANT. THE INPUT DATA REPORT ATTACHED AS REQUIRED
 IS NOT COMPLETE.
 FOR ONE EXAMPLE: PLEASE SEE THE IDR AS THIS SHOWS NO
 EXTERIOR LIGHTING. THIS SECTION OF THE IDR IS *BLANK*.
 HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE
 MANY EXTERIOR FIXTURES?
 PLEASE SEE FBC 13-415.2.ABC.1.3 FOR LIGHTING
 PERFORMANCE CALCULATIONS FOR EXTERIOR.
 PLEASE ALSO SEE FBC 13-415.2.ABC.1.1, .1.2 FOR INTERIOR
 LIGHTING.
  
 FOR EXAMPLE: THE FIXTURE WATTAGES LISTED ON THE IDR ARE
 NOT ALL THE SAME AS SHOWN ON THE FIXTURE LEGEND. THERE
 ARE SEVERAL INCONSISTENCIES.
  
  
 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70
 2003 NFPA-101
 2004 FBC W/2007 REVISIONS.
  
 5) NOTE: ALL LOW VOLTAGE SECURITY CAMERAS ETC WILL BE
 UNDER SEPARATE PERMITS WITH PLANS AND FEES.
  
 6) NOTE: PLEASE COORDINATE ELECTRICAL RISER. AS
 SUBMITTED THERE ARE SEVERAL ITEMS WHICH NEED TO BE
 ADDRESSED.
 THE NEW PANEL *D* IS BEING SHOWN WITH A LOAD WHICH FAR
 EXCEEDS THE RATING OF THE FEEDERS AND BREAKERS SHOWN IN
 PANEL *A*. IN FACT PANEL *A* SHOWS ONLY A 30AMP BREAKER
 AND FEEDERS WHEN IN FACT PANEL *D* HAS A LOAD OF 120.5
 AMPS.
 PLEASE ALSO SEE THE FEEDERS AS NOTED ON PANEL *D* ARE
 SHOWN AS 3/0 WHEN THE RISER SHOWS THESE AS 1/0. IN
 EITHER CASE BOTH OF THESE WOULD BE CODE COMPLIANCE
 BASED ON LOAD HOWEVER COORDINATION IS NEEDED WITH OVER
 CURRENT PROTECTION ETC.
 PLEASE SEE THE FEEDERS NOTED ON PANEL *A* ARE SHOWN AS
 500MCM IN A 3INCH CONDUIT, YET THE RISER SHOWS THE SAME
 CONDUCTORS IN A 2 INCH CONDUIT.
  
 7) NOTE: PLEASE INCLUDE NOTES FOR CONTRACTOR TO LABEL
 ALL MAINS FOR SERVICE PER 230.2E
  
 8) NOTE: PLEASE SHOW ALL EQUIPMENT GROUNDING PATHS/
 METHODS AFTER THE FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE SEE 210.8B2 AS ALL 15,20AMP 120V
 RECEPTACLES SERVING KITCHEN AREAS WHETHER OR NOT
 FEEDING APPLIANCES OR EQUIPMENT ON THE COUNTER AREAS
 WILL BE REQUIRED TO BE GFI OR GFI PROTECTED WITH CLASS
 A PROTECTION.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED OR INCOMPLETE ON PLANS THERE MAY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT POSSIBLY
 BE MADE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  