Plan Review Notes
Plan Review Notes For Permit 08090363
Permit Number 08090363
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-30 11:17:56BUILDING PLAN REVIEW
 PERMIT: 08090363
 ADD: 701 BELVEDERE RD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE REVISE SHEET
 A1 TO THE CURRENT 2007 SUPPLEMENTS.
  
 1D) SHETT A-1 UNDER THE HEADING BUILDING DATA WHERE THE
 CURRENT CODES ARE LISTED, PLANS FAIL TO IDENTIFY THE
 2004FBC EXISTING BUILDING WITH 2007 SUPPLEMENTS NOR THE
 LEVEL OF ALTERATION HAS NOT BEEN DECLARED BY THE DESIGN
 PROFESSIONAL 2004 FBC EXIST. SECTION 301.5.
  
 2) SHEET A1 INDICATES A SECTION 4 OF A4 PLANS DO NOT
 PROVIDE WHAT THE HEIGHT DIFFERENCE IS IN THE FRONT CURB
 AND ACCESSIBLE RAMP AREAS. IT CAN NOT BE DETERMINED IF
 THERE IS A GREATER THAN 6" DIFFERENCE IN GRADE THAT
 ENACT 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER
 THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 3) SHEET A-1 WALK IN COOLERS & FREEZERS THE TOTAL
 SQUARE FOOTAGE OF THE WALK-IN UNITS IS APPROX 417 SQ
 FT. 2603.4.1.3 LIMITS THE THE AGGREGATE FLOOR AREA TO
 400 SQ FT. PLEASE MODIFY, 2603.4.1.3.
 NOTE THAT THE ACTUAL COOLER AND MECHANICAL EQUIPMENT
 WILL REQUIRE A SEPERATE PERMIT WHERE AS THE REMAINDER
 OF THE REQUIREMENTS OF 2603.4.1.3 WILL NEED TO BE MET.
 SEPERATE REVIEWS WITH ASSOCIATED FEES WILL THEN OCCUR.
  
 4) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 4A) STORM SHUTTERS- THE REPORT SUBMITTED 02-0809.02
 EXPIRED 10/10/07 WILL REQUIRE NEW REPORT RULE 9B-72
 (31) ( E)
 4B) PRE-ENGINEERED A/C STANDS RULE 9B-72(31)(G)
  
 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS A COMPLETE INSTALLATION INSTALLATION SCHEDULE
 FOR SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING.
  
 FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
 A SAMPLE STORM SHUTTER SCHEDULE IS ATTACHED.
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1, ADMINISTRATIVE CODE2004 EDITION AS AMENDED
 BY THE CITY OF WEST PALM BEACH, PROVIDES THE ABILITY
 FOR THE BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 7) BOTH SHEETS A1 & A7 INDICATE A T8 FUTURE DEAL DWAWER
 BUT NO INFORMATION HAS BEEN PROVIDED PRODUCT
 INFORMATION, THE SECURING INTO THE STRUCTURAL SHELL OF
 THE BUILDING.1609.6.1.2. COMPONENTS AND CLADDING.
  
 8) SHEET A-1 MISSING THE REQUIRED 18" BETWEEN THE WATER
 COOLER AND LATCH SIDE OF THE RESTROOM DOOR. 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 9) SHEET A4 DETAIL 2 THE COUNTER HEIGHT IS 36" BUT THE
 COUNTER HEIGHT SHOULD BE 34" SECTION 11-5.2.
  
 10) THE ENRGY CALCULATIONS INDICATE THE USE OF 3"
 ICYNENE INSULATION AT THE CONCRETE DOUBLE TEE ROOF
 SYSTEM PROVIDING A R VALUE OF 12.3. PLEASE REVIEW
 2603.5.2 AND REQUIRED THERMAL BARRIER MEETING THE
 PROVISIONS OF SECTION 2603.4 .
  
 11A) THE ENERGY CALCULATIONS ALSO INDICATE A R-VALUE OF
 5.73 FOR A CONCRETE FLOOR WITH CARPET AND RUBBER
 PADDING. 804.5.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH IN VERTICAL EXITS, EXIT
 PASSAGEWAYS AND EXIT ACCESS CORRIDORS SHALL NOT BE LESS
 THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
 IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL
 COMPLY WITH THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
  
 11B) 11-4.5.3 CARPET . IF CARPET OR CARPET TILE IS USED
 ON A GROUND OR FLOOR SURFACE, THEN IT SHALL BE SECURELY
 ATTACHED; HAVE A FIRM CUSHION, PAD, OR BACKING, OR NO
 CUSHION OR PAD; AND HAVE A LEVEL LOOP, TEXTURED LOOP,
 LEVEL CUT PILE, OR LEVEL CUT/UNCUT PILE TEXTURE. THE
 MAXIMUM PILE THICKNESS SHALL BE ? INCH (13 MM) [SEE
 FIGURE 8 (F)]. EXPOSED EDGES OF CARPET SHALL BE
 FASTENED TO FLOOR SURFACES AND HAVE TRIM ALONG THE
 ENTIRE LENGTH OF THE EXPOSED EDGE. CARPET EDGE TRIM
 SHALL COMPLY WITH SECTION 11-4.5.2 . PLEASE PROVIDE
 MANUFACTURERS INFORMATION ON CARPET AND PAD.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  