| 2008-09-30 09:51:00 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE CLEAR AND LEGIBLE DRAWINGS. DRAWINGS FOR |
| | STORM PANELS ARE NOT LEGIBLE. |
| | |
| | 2- STORM PANELS: |
| | A) USE TABLE R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE |
| | (OR TABLE R301.2(3) WHEN PROPERTY IS LOCATED ON |
| | EXPOSURE "C") FOR THE OPENINGS DESIGN PRESSURES. |
| | OTHERWISE, DESIGN PRESSURES SUBMITTED NEED TO BE SIGNED |
| | AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE. SEE ATTACHED COPIES OF REFERENCED |
| | TABLES. |
| | |
| | B) ANCHOR HIGHLIGHTED ON SHEET 1 OF SHUTTER DRAWINGS IS |
| | DIFFERENT FROM THAT ONE SPECIFIED ON INSTALLATION |
| | SCHEDULE. REVISE/CLARIFY AS REQUIRED. |
| | |
| | C) CLARIFY WHY THE SHUTTER SPAN SHOWN ON THE |
| | INSTALLATION SCHEDULE IS ALMOST DOUBLE AS THE OPENING |
| | SIZE SHOWN ON OPENING SIZE COLUMN. |
| | |
| | D) DESIGN PRESSURES SHOWN ON INSTALLATION SCHEDULE ARE |
| | DIFFERENT FROM THOSE HIGHLIGHTED ON THE DESIGN PRESSURE |
| | CALCULATIONS SUBMITTED. CLARIFY/REVISE AS REQUIRED. |
| | |
| | E) EDGE DISTANCE SHOWN ON THE INSTALLATION SCHEDULE |
| | CAN'T BE ONLY 1". SEE SHUTTERS DRAWINGS FOR MINIMUM |
| | EDGE DISTANCE REQUIRED AND PROPER FACTOR TO BE USED FOR |
| | REDUCED ANCHOR SPACING. IN ADDITION THIS NUMBER DOESN'T |
| | MATCH INFORMATION PROVIDED ON PANEL SPAN COLUMN. |
| | |
| | F) DETAIL #13 ON SHEET 8 OF STORM SHUTTERS DRAWINGS |
| | REQUIRES POURED CONCRETE. INSTALLATION SCHEDULE CALLS |
| | FOR CONCRETE BLOCK AS THE SUBSTRATE TO RECEIVE THE |
| | PANELS. THIS DETAIL DOESN'T APPLY TO CONCRETE BLOCK |
| | INSTALLATIONS. REVISE AS REQUIRED. |
| | |
| | 3- ACCORDION SHUTTERS: |
| | A) HIGHLIGHTED TABLES ON SHEET 7 OF ACCORDION SHUTTERS |
| | DRAWINGS ARE HIGHLIGHTED INCORRECTLY. THE SLAT SPAN |
| | DOESN'T REPRESENT THE PANEL SPAN SHOWN ON INSTALLATION |
| | SCHEDULE. REVISE AS REQUIRED. ALSO, REFERENCE CONCRETE |
| | BLOCK TABLES AS SPECIFIED ON INSTALLATION SCHEDULE. |
| | |
| | B) CLARIFY HOW IS THE REAR DOOR USED AS EMERGENCY |
| | EGRESS. IS THE DOOR INSWING OR OUTSWING. AND ARE THE |
| | ACCORDION SHUTTERS INSTALLED WITH THE INSIDE LOCK?. |
| | |
| | C) CLARIFY WHY PANEL SPAN IS ALMOST DOUBLE AS THE |
| | OPENING SIZE? |
| | |
| | D) EDGE DISTANCE SHOWN ON THE INSTALLATION SCHEDULE |
| | DOESN'T REPRESENT SIZE SPECIFIED ON THE PANEL SPAN. |
| | REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |