2008-09-30 09:51:00RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PROVIDE CLEAR AND LEGIBLE DRAWINGS. DRAWINGS FOR
 STORM PANELS ARE NOT LEGIBLE.
  
 2- STORM PANELS:
 A) USE TABLE R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE
 (OR TABLE R301.2(3) WHEN PROPERTY IS LOCATED ON
 EXPOSURE "C") FOR THE OPENINGS DESIGN PRESSURES.
 OTHERWISE, DESIGN PRESSURES SUBMITTED NEED TO BE SIGNED
 AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE. SEE ATTACHED COPIES OF REFERENCED
 TABLES.
  
 B) ANCHOR HIGHLIGHTED ON SHEET 1 OF SHUTTER DRAWINGS IS
 DIFFERENT FROM THAT ONE SPECIFIED ON INSTALLATION
 SCHEDULE. REVISE/CLARIFY AS REQUIRED.
  
 C) CLARIFY WHY THE SHUTTER SPAN SHOWN ON THE
 INSTALLATION SCHEDULE IS ALMOST DOUBLE AS THE OPENING
 SIZE SHOWN ON OPENING SIZE COLUMN.
  
 D) DESIGN PRESSURES SHOWN ON INSTALLATION SCHEDULE ARE
 DIFFERENT FROM THOSE HIGHLIGHTED ON THE DESIGN PRESSURE
 CALCULATIONS SUBMITTED. CLARIFY/REVISE AS REQUIRED.
  
 E) EDGE DISTANCE SHOWN ON THE INSTALLATION SCHEDULE
 CAN'T BE ONLY 1". SEE SHUTTERS DRAWINGS FOR MINIMUM
 EDGE DISTANCE REQUIRED AND PROPER FACTOR TO BE USED FOR
 REDUCED ANCHOR SPACING. IN ADDITION THIS NUMBER DOESN'T
 MATCH INFORMATION PROVIDED ON PANEL SPAN COLUMN.
  
 F) DETAIL #13 ON SHEET 8 OF STORM SHUTTERS DRAWINGS
 REQUIRES POURED CONCRETE. INSTALLATION SCHEDULE CALLS
 FOR CONCRETE BLOCK AS THE SUBSTRATE TO RECEIVE THE
 PANELS. THIS DETAIL DOESN'T APPLY TO CONCRETE BLOCK
 INSTALLATIONS. REVISE AS REQUIRED.
  
 3- ACCORDION SHUTTERS:
 A) HIGHLIGHTED TABLES ON SHEET 7 OF ACCORDION SHUTTERS
 DRAWINGS ARE HIGHLIGHTED INCORRECTLY. THE SLAT SPAN
 DOESN'T REPRESENT THE PANEL SPAN SHOWN ON INSTALLATION
 SCHEDULE. REVISE AS REQUIRED. ALSO, REFERENCE CONCRETE
 BLOCK TABLES AS SPECIFIED ON INSTALLATION SCHEDULE.
  
 B) CLARIFY HOW IS THE REAR DOOR USED AS EMERGENCY
 EGRESS. IS THE DOOR INSWING OR OUTSWING. AND ARE THE
 ACCORDION SHUTTERS INSTALLED WITH THE INSIDE LOCK?.
  
 C) CLARIFY WHY PANEL SPAN IS ALMOST DOUBLE AS THE
 OPENING SIZE?
  
 D) EDGE DISTANCE SHOWN ON THE INSTALLATION SCHEDULE
 DOESN'T REPRESENT SIZE SPECIFIED ON THE PANEL SPAN.
 REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  