| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING:THE SAME COMMENTS FROM THE PREVIOUS REVIEW |
| | WHERE NOT RESPONDED TO, PLEASE REMOVE ALL OLD OR VOIDED |
| | SHEETS AND REPLACE WITH CORRECTED ONES WHEN |
| | RESUBMITTING. INCLUDE THEM SEPARATELY TO EXPEDITE THE |
| | REVIEW PROCESS. RESPOND TO REVIEW COMMENTS IN WRITING. |
| | |
| | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). INDICATE THAT CIRCUIT ON |
| | THE PANEL SCHEDULE, AND THE GFI'S ON THE FLOOR PLAN*** |
| | NOT IN THE PANEL SCHEDULE |
| | |
| | 3} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER |
| | 61G15-23.002(2) FAC. IS REQUIRED***THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER MUST APPEAR IN THE COMPANY TITLE |
| | BLOCK.. |
| | |
| | 4} NEW COMMENT THIS SET OF PLANS: RECEPTACLE SPACING |
| | MUST COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005 |
| | NEC*** INDICATE COMPLIANCE ON THE PLAN |
| | |
| | 5} 210.70(A)(2)(B) FOR DWELLING UNITS, ATTACHED |
| | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT |
| | LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL |
| | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR |
| | SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL |
| | ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE |
| | CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT*** THESE |
| | LIGHTS WERE ON THE EXISTING BUILDING , BUT NEED TO BE |
| | SHOWN ON THE "NEW ELECTRIC PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |