 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:THE SAME COMMENTS FROM THE PREVIOUS REVIEW
 WHERE NOT RESPONDED TO, PLEASE REMOVE ALL OLD OR VOIDED
 SHEETS AND REPLACE WITH CORRECTED ONES WHEN
 RESUBMITTING. INCLUDE THEM SEPARATELY TO EXPEDITE THE
 REVIEW PROCESS. RESPOND TO REVIEW COMMENTS IN WRITING.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE THAT CIRCUIT ON
 THE PANEL SCHEDULE, AND THE GFI'S ON THE FLOOR PLAN***
 NOT IN THE PANEL SCHEDULE
  
 3} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER
 61G15-23.002(2) FAC. IS REQUIRED***THE CERTIFICATE OF
 AUTHORIZATION NUMBER MUST APPEAR IN THE COMPANY TITLE
 BLOCK..
  
 4} NEW COMMENT THIS SET OF PLANS: RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005
 NEC*** INDICATE COMPLIANCE ON THE PLAN
  
 5} 210.70(A)(2)(B) FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT
 LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL
 ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT*** THESE
 LIGHTS WERE ON THE EXISTING BUILDING , BUT NEED TO BE
 SHOWN ON THE "NEW ELECTRIC PLAN.
  