| Date |
Text |
| 2008-09-17 16:54:41 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 1 OF 2, SANITARY PLUMBING RISER: THE FOLLOWING |
| | ITEMS NEED CORRECTING PER THE FBC-2004 PLUMBING |
| | SECTIONS. |
| | |
| | A} THE 1-1/2" WASTE ARM FOR THE PROPOSED LAVATORY IS TO |
| | FAR FROM THE VENT. AN 1-1/2" WASTE ARM WITH AN 1-1/2" |
| | TRAP CAN ONLY BE 5' FROM THE VENT. A 2" WASTE ARM WITH |
| | AN 1-1/2" TRAP CAN ONLY BE 6' FROM THE VENT. PLEASE |
| | KNOW THAT PER 1/4" = 1' SCALE THE DEVELOPED LENGTH OF |
| | THE LAVATORY WASTE ARM IS ABOUT 7'. PER TABLE 906.1 |
| | MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT. |
| | |
| | B} THE PROPOSED SINK IS INDICATING AN ISLAND VENT. |
| | PLEASE REFERENCE THE FOLLOWING CODE SECTIONS AND COMPLY |
| | FOR THE ISLAND VENT ALSO PLEASE REFERENCE FIGURE 913.2 |
| | ISLAND FIXTURE VENT ATTACHED TO THESE COMMENTS FOR THE |
| | RESUBMITTAL. |
| | |
| | SECTION 913.2 VENT CONNECTION. |
| | THE ISLAND FIXTURE VENT SHALL CONNECT TO THE FIXTURE |
| | DRAIN AS REQUIRED FOR AN INDIVIDUAL OR COMMON VENT. THE |
| | VENT SHALL RISE VERTICALLY TO ABOVE THE DRAINAGE OUTLET |
| | OF THE FIXTURE BEING VENTED BEFORE OFFSETTING |
| | HORIZONTALLY OR VERTICALLY DOWNWARD. THE VENT OR BRANCH |
| | VENT FOR MULTIPLE ISLAND FIXTURE VENTS SHALL EXTEND TO |
| | A MINIMUM OF 6 INCHES (152 MM) ABOVE THE HIGHEST ISLAND |
| | FIXTURE BEING VENTED BEFORE CONNECTING TO THE OUTSIDE |
| | VENT TERMINAL. |
| | |
| | SECTION 913.3 VENT INSTALLATION BELOW THE FIXTURE FLOOD |
| | LEVEL RIM. |
| | THE VENT LOCATED BELOW THE FLOOD LEVEL RIM OF THE |
| | FIXTURE BEING VENTED SHALL BE INSTALLED AS REQUIRED FOR |
| | DRAINAGE PIPING IN ACCORDANCE WITH CHAPTER 7 , EXCEPT |
| | FOR SIZING. THE VENT SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION 916.2 . THE LOWEST POINT OF THE ISLAND FIXTURE |
| | VENT SHALL CONNECT FULL SIZE TO THE DRAINAGE SYSTEM. |
| | THE CONNECTION SHALL BE TO A VERTICAL DRAIN PIPE OR TO |
| | THE TOP HALF OF A HORIZONTAL DRAIN PIPE. CLEANOUTS |
| | SHALL BE PROVIDED IN THE ISLAND FIXTURE VENT TO PERMIT |
| | RODDING OF ALL VENT PIPING LOCATED BELOW THE FLOOD |
| | LEVEL RIM OF THE FIXTURES. RODDING IN BOTH DIRECTIONS |
| | SHALL BE PERMITTED THROUGH A CLEANOUT. |
| | |
| | NOTE: IT IS SUGGESTED THAT AN AIR ADMITTACE VALVE BE |
| | USED FOR THE PROPOSED SINK. PER SECTION 917 AIR |
| | ADMITTANCE VALVES. |
| | |
| | C} CLEARLY INDICATE THAT A TWO-WAY CLEANOUT WILL BE |
| | INSTALLED AT THE JUNCTION OF THE BUILDING DRAIN AND |
| | BUILDING SEWER. PER SECTION 708.3.5 JUNCTION OF |
| | BUILDING DRAIN AND BUILDING SEWER. |
| | |
| | 2. INFORMATION MISSING FROM TITLE BLOCK ON ALL SHEETS. |
| | SEE FAC 61G15-23.002 (2) A TITLE BLOCK ON EACH SHEET |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| | |
| | 3. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT |
| | IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE - |
| | 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY.. PER FS |
| | 713.13 (2): IF THE IMPROVEMENT DESCRIBED IN THE NOTICE |
| | OF COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 |
| | DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID |
| | AND OF NO FURTHER EFFECT. |
| | |
| | 4. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007 |
| | REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5 |
| | RETENTION OF CONSTRUCTION DOCUMENTS. |
| | |
| | 5. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |