Plan Review Notes
Plan Review Notes For Permit 08090338
Permit Number 08090338
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-25 16:30:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE THAT CIRCUIT ON
 THE PANEL SCHEDULE, AND THE GFI'S ON THE FLOOR PLAN.
  
 2} 210.8(A)(7) LAUNDRY, UTILITY, AND WET BAR SINKS ?
 WHERE THE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK MUST BE GFI PROTECTED.
  
 3} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER
 61G15-23.002(2) FAC. IS REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  