| 2008-09-25 16:30:49 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). INDICATE THAT CIRCUIT ON | | | THE PANEL SCHEDULE, AND THE GFI'S ON THE FLOOR PLAN. | | | | | | 2} 210.8(A)(7) LAUNDRY, UTILITY, AND WET BAR SINKS ? | | | WHERE THE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) | | | OF THE OUTSIDE EDGE OF THE SINK MUST BE GFI PROTECTED. | | | | | | 3} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER | | | 61G15-23.002(2) FAC. IS REQUIRED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|