| 2008-09-17 07:52:02 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT T REFERENCE STANDARDS SHALL INCLUDE THE 2007 |
| | REVISIONS TO THE 2004 FLORIDA BUILDING CODE. |
| | |
| | 2. SHT A-1 DEMO NOTES #4. PLEASE SHOW WHERE THE |
| | PLUMBING WASTE LINES ARE TO BE CAPPED. IN THE REMOVAL |
| | OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| | PROHIBITED. SECTION 704.5. ALL DEMO'D/CAPPED LINES |
| | SHALL BE INSPECTED PRIOR TO COVERING. |
| | |
| | 3. SHT A-3 NOTE FOR BREAK ROOM SINK INDICATES CABINET |
| | DOORS AT THE SINK. THIS IS NOT APPROVED AS DOORS SHALL |
| | NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY |
| | FIXTURE. THE SINK SHALL BE ACCESSIBLE, NOT ADAPTABLE. |
| | CLEAR FLOOR SPACE SHALL BE UNOBSTRUCTED. SECTION 11-3. |
| | PLEASE DELETE NOTE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |