2008-09-23 11:12:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2: FLOOR PLANS SHOWS DUCT SMOKE DETECTOR ONLY
 ON HP-5. HOWEVER, ALL HEAT PUMPS IN THIS SPACE SHARE A
 COMMON RETURN AIR PLENUM. THEREFORE, EACH UNIT SHALL BE
 PROTECTED BY DUCT SMOKE DETECTOR IN ACCORDANCE WITH
 FBCM 606.2.2.
 NOTE: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBCM
 606.4.1.
  
 2. OUTSIDE AIR INTAKES SHALL BE PROVIDED WITH SHUTOFF
 DAMPER CONTROLS IN ACCORDANCE WITH FBCB
 13-409.1.ABC.3.3.
  
 3. EACH HYDRONIC HEAT PUMP SHALL HAVE A TWO-POSITION
 AUTOMATIC VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN
 THE COMPRESSOR IS OFF IN ACCORDANCE WITH FBCB
 13-411.1.ABC.1.4.
  
 4. PAGE M-3 CEILING DIFFUSER DETAIL PLACES A MAXIMUM
 LENGTH LIMIT OF 8 FEET FOR FLEXIBLE DUCTS. SEVERAL FLEX
 DUCTS ON FLOOR PLAN (PAGE M-2) ARE SHOWN TO BE WELL IN
 EXCESS OF THIS LIMIT. PLEASE COORDINATE DETAILS AND
 FLOOR PLANS AND CLARIFY THE INTENT. FBCM 603.1 AND FBCB
 106.1.1
  