| Plan Review Notes For Permit 08090337 |
| Permit Number |
08090337 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-23 11:12:16 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-2: FLOOR PLANS SHOWS DUCT SMOKE DETECTOR ONLY | | | ON HP-5. HOWEVER, ALL HEAT PUMPS IN THIS SPACE SHARE A | | | COMMON RETURN AIR PLENUM. THEREFORE, EACH UNIT SHALL BE | | | PROTECTED BY DUCT SMOKE DETECTOR IN ACCORDANCE WITH | | | FBCM 606.2.2. | | | NOTE: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE | | | BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBCM | | | 606.4.1. | | | | | | 2. OUTSIDE AIR INTAKES SHALL BE PROVIDED WITH SHUTOFF | | | DAMPER CONTROLS IN ACCORDANCE WITH FBCB | | | 13-409.1.ABC.3.3. | | | | | | 3. EACH HYDRONIC HEAT PUMP SHALL HAVE A TWO-POSITION | | | AUTOMATIC VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN | | | THE COMPRESSOR IS OFF IN ACCORDANCE WITH FBCB | | | 13-411.1.ABC.1.4. | | | | | | 4. PAGE M-3 CEILING DIFFUSER DETAIL PLACES A MAXIMUM | | | LENGTH LIMIT OF 8 FEET FOR FLEXIBLE DUCTS. SEVERAL FLEX | | | DUCTS ON FLOOR PLAN (PAGE M-2) ARE SHOWN TO BE WELL IN | | | EXCESS OF THIS LIMIT. PLEASE COORDINATE DETAILS AND | | | FLOOR PLANS AND CLARIFY THE INTENT. FBCM 603.1 AND FBCB | | | 106.1.1 | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|