2008-10-21 15:19:55*****DENIED*****
  
  
 1. FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE
 REFERENCED, NOT 2002 AS LISTED IN THE REFERENCED
 STANDARDS ON COVER SHEET T.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH DAY OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 ACCESS TO / EGRESS FROM THE SAID FLOOR OR THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED
  
  