| 2008-09-17 17:05:16 | RESIDENTIAL (R3) REPAIRS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE 2 COPIES OF PRODUCT APPROVAL FOR FLAT ROOF |
| | SYSTEM AS REQUIRED BY DCA RULE 9B-72. |
| | NOTE: CLEARLY MARK SPECIFIC APPROVED FLAT ROOF ASSEMBLY |
| | TO BE USED AND SPECIFIC BASE SHEET FASTENING OPTION. |
| | ALSO, PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING |
| | AT PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION |
| | #7. |
| | CALL IF YOU HAVE ANY QUESTIONS REGARDING THIS PRODUCT |
| | APPROVAL AND RAS 117 CALCULATIONS. |
| | SEE ATTACHED COPY OF CITY POLICY FOR ROOFING PERMITS |
| | AND INFORMATION REQUIRED TO BE SUBMITTED. |
| | |
| | 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | NEED TO UPGRADE VALUE TO INCLUDE ALL LABOR AND |
| | MATERIALS. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | 4- REVISE TYPE AND NAIL SPACING FOR ROOF SHEATHING AS |
| | REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. NEED TO USE 8D RING SHANK NAILS AND NAIL SPACING |
| | IN ROOF ZONE 3 IS 4" OF CENTER. REVISE AS REQUIRED. |
| | |
| | 5- THERE ARE ONLY 3 ANCHOR BOLTS HOLDING THE 2X10 WOOD |
| | PLATE. PROVIDE CALCULATIONS SHOWING HOW THIS THREE |
| | ANCHORS WILL RESIST THE UPLIFT LOAD CREATED BY THE 140 |
| | MPH WIND LOADS. ALSO, SPECIFY WHAT IS THE MINIMUM |
| | DISTANCE REQUIRED TO BE AT THE ENDS OF THE 2X10 PLATE. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY |
| | COMPLIANCE WITH THE UPLIFT LOADS OF SEC. R301 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- PROVIDE DETAIL SHOWING HOW IS THE MSTAM24 SIMPSON |
| | STRAP GOING TO BE INSTALLED. SEE SIMPSON CATALOG FOR |
| | SPECIFIC INSTALLATION THAT STRAP WAS DESIGNED FOR. |
| | PROVIDE COMPLETE ENGINEERING ANALYSIS FOR USE OTHER |
| | THAN THAT SHOWN ON THE SIMPSON CATALOG. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH |
| | SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- ROOF FRAMING PLAN AND BUILDING SECTION 1/R-1 DON'T |
| | MATCH. REVISE AS REQUIRED TO MATCH. CHECK NUMBER OF |
| | JOISTS AND OVERHANG DETAIL AND REVISE AS REQUIRED. |
| | |
| | 8- SPECIFY ROOF SLOPE TO VERIFY COMPLIANCE WITH SEC. |
| | R905.11 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- INFORMATION ON WALL SECTION 2/R-1 DOESN'T MATCH |
| | INFORMATION SHOWN ON ROOF FRAMING PLAN. WALL SECTION |
| | CALLS FOR SIMPSON HM9 CONNECTORS AT THE EXISTING WALL |
| | END, WHILE ROOF FRAMING PLAN CALLS FOR SIMPSON H3 |
| | CONNECTORS. REVISE AS REQUIRED TO MATCH. |
| | |
| | 10- ROOFING PERMIT IS REQUIRED FOR SCOPE OF WORK TO BE |
| | PERFORMED. SIGN PERMIT APPLICATION ON SPACE ALOCATED |
| | FOR THE ROOFING CONTRACTOR. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |