Plan Review Notes
Plan Review Notes For Permit 08090322
Permit Number 08090322
Review Stop B
Sequence Number 3
Notes
Date Text
2008-12-17 15:00:162004 FBC W/2007 REVISIONS
 ADDITION
  
 REVISION IS DENIED BY BUILDING
  
 1) THE REVISED PLANS DO NOT SPECIFY THE SIZE AND
 SPECIES OF WOOD THAT IS REQUIRED FOR THE CEILING JOISTS
 IN THE PORTION OF THE ADDITION WITH THE FLAT CEILING.
 R802.2.2
  
 2) SPECIFY THE SPECIES OF WOOD REQUIRED FOR THE
 RAFTERS. R802.2.3
  
 3) THE BUILDING AND WALL SECTIONS ON ARCHITECTURAL
 SHEETS A4 AND A5 SHOULD BE REVISED TO SHOW THE
 CONVENTIONAL ROOF FRAMING AT 16" OC RATHER THAN THE
 SCISSOR TRUSSES AT 24" OC. R801.2
  
 4) THE REVISED DETAIL 3 ON S-3 SPECIFIES VCT2 ANCHORS
 AT 48" OC AT THE PIGGY BACK RAFTERS. HOW WILL THIS WORK
 AS THE RAFTERS WILL NOT HAVE A BOTTOM CORD. A 2 X
 NAILED TO THE TOP OF THE EXISTING TRUSSES AT THE VALLEY
 FOR THE RAFTERS TO BEAR ON OR 2 X BLOCKING NAILED
 BETWEEN THE RAFTERS AT THE VALLEY WILL BE REQUIRED. THE
 RAFTER WILL NEED TO BE ANCHORED TO THE EXISTING
 TRUSSES. PLEASE REVISE. R802.2.4 AND R802.2.2.9.1
  
 5) SPECIFY WHERE THE EXTERIOR WALL SECTION DETAIL IN
 THE 8-1/2" X 11" DRAWING OCCURS. AN EXISTING FOOTING IS
 SHOWN AT THE EXTERIOR WALL. THIS CONDITION DOES NOT
 APPEAR TO BE INDICATED BY THE FOUNDATION PLAN ON SHEET
 S-1. R401.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]