| Notes |
| Date |
Text |
| 2008-12-17 15:00:16 | 2004 FBC W/2007 REVISIONS | | | ADDITION | | | | | | REVISION IS DENIED BY BUILDING | | | | | | 1) THE REVISED PLANS DO NOT SPECIFY THE SIZE AND | | | SPECIES OF WOOD THAT IS REQUIRED FOR THE CEILING JOISTS | | | IN THE PORTION OF THE ADDITION WITH THE FLAT CEILING. | | | R802.2.2 | | | | | | 2) SPECIFY THE SPECIES OF WOOD REQUIRED FOR THE | | | RAFTERS. R802.2.3 | | | | | | 3) THE BUILDING AND WALL SECTIONS ON ARCHITECTURAL | | | SHEETS A4 AND A5 SHOULD BE REVISED TO SHOW THE | | | CONVENTIONAL ROOF FRAMING AT 16" OC RATHER THAN THE | | | SCISSOR TRUSSES AT 24" OC. R801.2 | | | | | | 4) THE REVISED DETAIL 3 ON S-3 SPECIFIES VCT2 ANCHORS | | | AT 48" OC AT THE PIGGY BACK RAFTERS. HOW WILL THIS WORK | | | AS THE RAFTERS WILL NOT HAVE A BOTTOM CORD. A 2 X | | | NAILED TO THE TOP OF THE EXISTING TRUSSES AT THE VALLEY | | | FOR THE RAFTERS TO BEAR ON OR 2 X BLOCKING NAILED | | | BETWEEN THE RAFTERS AT THE VALLEY WILL BE REQUIRED. THE | | | RAFTER WILL NEED TO BE ANCHORED TO THE EXISTING | | | TRUSSES. PLEASE REVISE. R802.2.4 AND R802.2.2.9.1 | | | | | | 5) SPECIFY WHERE THE EXTERIOR WALL SECTION DETAIL IN | | | THE 8-1/2" X 11" DRAWING OCCURS. AN EXISTING FOOTING IS | | | SHOWN AT THE EXTERIOR WALL. THIS CONDITION DOES NOT | | | APPEAR TO BE INDICATED BY THE FOUNDATION PLAN ON SHEET | | | S-1. R401.2 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|