| 2008-10-15 11:59:16 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | DUE TO THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON |
| | SHEET P-2 THE FOLLOWING CORRECTIONS/INFORMATION ARE |
| | REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE |
| | AND THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE.. |
| | **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON |
| | SHEET P-2 DOES NOT INDICATE THE CORRESPONDING LENGTH TO |
| | CUT SECTION OF PIPE TO THE NEW RANGE RISER. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON |
| | SHEET P-2 DOES NOT INDICATE THE GAS PIPE SIZES TO THE |
| | NEW RANGE. |
| | |
| | 3. SHEET P-2 GAS ISOMETRIC: THE GAS PIPE SIZE OF 3/4" |
| | TO THE NEW INST. HOT (TANKLESS WATER HEATER) IS SIZED |
| | WRONG. PER TABLE 402.4(2) SCH. 40 METALLIC PIPE, WITH A |
| | LONGEST LENGTH OF 40' AND WITH 189,000 BTU'S THE GAS |
| | PIPING TO THE NEW INST. HOT (TANKLESS WATER HEATER) |
| | SHALL BE 1". PLEASE REFERENCE FBC-2004 FUEL GAS TABLE |
| | 402.4(2) ATTACHED TO THESE COMMENTS INDICATING THIS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |