Plan Review Notes
Plan Review Notes For Permit 08090322
Permit Number 08090322
Review Stop G
Sequence Number 2
Notes
Date Text
2008-10-15 11:59:16GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 DUE TO THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON
 SHEET P-2 THE FOLLOWING CORRECTIONS/INFORMATION ARE
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE
 AND THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE..
 **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON
 SHEET P-2 DOES NOT INDICATE THE CORRESPONDING LENGTH TO
 CUT SECTION OF PIPE TO THE NEW RANGE RISER.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 **NOTE: THE REDESIGNED RESUBMITTED GAS ISOMETRIC ON
 SHEET P-2 DOES NOT INDICATE THE GAS PIPE SIZES TO THE
 NEW RANGE.
  
 3. SHEET P-2 GAS ISOMETRIC: THE GAS PIPE SIZE OF 3/4"
 TO THE NEW INST. HOT (TANKLESS WATER HEATER) IS SIZED
 WRONG. PER TABLE 402.4(2) SCH. 40 METALLIC PIPE, WITH A
 LONGEST LENGTH OF 40' AND WITH 189,000 BTU'S THE GAS
 PIPING TO THE NEW INST. HOT (TANKLESS WATER HEATER)
 SHALL BE 1". PLEASE REFERENCE FBC-2004 FUEL GAS TABLE
 402.4(2) ATTACHED TO THESE COMMENTS INDICATING THIS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]