| 2008-09-23 12:54:33 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE INFORMATION SHOWING HOW THE EXHAUST FAN IS |
| | TO BE INTERLOCKED WITH THE SPRAYING EQUIPMENT. SPRAYING |
| | EQUIPMENT SHALL BE INTERLOCKED WITH THE VENTILATION OF |
| | THE SPRAYING AREA SUCH THAT SPRAYING OPERATIONS CANNOT |
| | BE CONDUCTED UNLESS THE VENTILATION SYSTEM IS IN |
| | OPERATION IN ACCORDANCE WITH FBCM 502.7.3.1. |
| | |
| | 2. PROVIDE INFORMATION SHOWING A TIME DELAY IN EFFECT |
| | TO ASSURE FAN RUNS FOR A PERIOD AFTER SPRAYING |
| | OPERATIONS HAVE STOPPED. MECHANICAL VENTILATION SHALL |
| | BE KEPT IN OPERATION FOR A SUFFICIENT TIME THEREAFTER |
| | TO ALLOW VAPORS FROM DRYING COATED ARTICLES AND |
| | FINISHING MATERIAL RESIDUE TO BE EXHAUSTED IN |
| | ACCORDANCE WITH FBCM 502.7.3.1. |
| | |
| | 3. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE |
| | EXHAUST TERMINATION WITH RESPECT TO PROPERTY LINES AND |
| | ADJACENT BUILDINGS. THE TERMINATION POINT FOR EXHAUST |
| | DUCTS DISCHARGING TO THE ATMOSPHERE SHALL BE LOCATED |
| | WITH THE FOLLOWING MINIMUM DISTANCES: |
| | |
| | - 30 FEET (9144 MM) FROM THE PROPERTY LINE; |
| | - 10 FEET (3048 MM) FROM OPENINGS INTO THE BUILDING; |
| | - 6 FEET (1829 MM) FROM EXTERIOR WALLS AND ROOFS; |
| | - 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND OPENINGS |
| | INTO THE BUILDING WHICH ARE IN THE DIRECTION OF THE |
| | EXHAUST DISCHARGE; |
| | - 10 FEET (3048 MM) ABOVE ADJOINING GRADE. |
| | |
| | 4. PROVIDE SPECIFICATIONS FOR THE EXHAUST FAN. ELECTRIC |
| | MOTORS DRIVING EXHAUST FANS SHALL NOT BE PLACED INSIDE |
| | DUCTS. FAN ROTATING ELEMENTS SHALL BE NONFERROUS OR |
| | NONSPARKING OR THE CASING SHALL CONSIST OF, OR BE LINED |
| | WITH, SUCH MATERIAL. BELTS SHALL NOT ENTER THE DUCT OR |
| | BOOTH UNLESS THE BELT AND PULLEY WITHIN THE DUCT ARE |
| | TIGHTLY ENCLOSED IN ACCORDANCE WITH FBCM 502.7.3.7. |
| | |
| | 5. EAST EXTERIOR ELEVATION IDENTIFIES THE EXHAUST |
| | TERMINATION AS A LOUVERED VENT. THIS APPEARS TO BE AN |
| | UP-TURNED 90 DEGREE ELBOW, NOT A LOUVER. PLEASE |
| | CLARIFY. ALSO, SEE COMMENT #3 ABOVE, THIS TERMINATION |
| | SHALL BE A MINIMUM OF 6 FEET FROM THE EXTERIOR OF THE |
| | BUILDING. SHOW WHAT TYPE OF WEATHERPROOF TERMINATION IS |
| | TO BE USED. EXHAUST OUTLETS SHALL BE PROTECTED AGAINST |
| | LOCAL WEATHER CONDITIONS IN ACCORDANCE WITH FBCM 401.6 |
| | |
| | 6: THE MAKE-UP AIR LOVER IS REQUIRED TO HAVE A PRODUCT |
| | APPROVAL IN ACCORDANCE WITH FBCB 1609 AND FAC RULE |
| | 9B-72. PROVIDE PRODUCT APPROVAL DOCUMENTATION APPROVED |
| | IN WRITING BY THE ARCHITECT IN ACCORDANCE WITH FBCB |
| | 106.3.3. |
| | |
| | 7. SHOW HOW THE EXTERIOR EXHAUST DUCT AND TERMINATION |
| | ARE TO BE SECURED AND INSTALLED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH FBCM 301.13. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |