2008-09-23 12:54:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE INFORMATION SHOWING HOW THE EXHAUST FAN IS
 TO BE INTERLOCKED WITH THE SPRAYING EQUIPMENT. SPRAYING
 EQUIPMENT SHALL BE INTERLOCKED WITH THE VENTILATION OF
 THE SPRAYING AREA SUCH THAT SPRAYING OPERATIONS CANNOT
 BE CONDUCTED UNLESS THE VENTILATION SYSTEM IS IN
 OPERATION IN ACCORDANCE WITH FBCM 502.7.3.1.
  
 2. PROVIDE INFORMATION SHOWING A TIME DELAY IN EFFECT
 TO ASSURE FAN RUNS FOR A PERIOD AFTER SPRAYING
 OPERATIONS HAVE STOPPED. MECHANICAL VENTILATION SHALL
 BE KEPT IN OPERATION FOR A SUFFICIENT TIME THEREAFTER
 TO ALLOW VAPORS FROM DRYING COATED ARTICLES AND
 FINISHING MATERIAL RESIDUE TO BE EXHAUSTED IN
 ACCORDANCE WITH FBCM 502.7.3.1.
  
 3. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE
 EXHAUST TERMINATION WITH RESPECT TO PROPERTY LINES AND
 ADJACENT BUILDINGS. THE TERMINATION POINT FOR EXHAUST
 DUCTS DISCHARGING TO THE ATMOSPHERE SHALL BE LOCATED
 WITH THE FOLLOWING MINIMUM DISTANCES:
  
 - 30 FEET (9144 MM) FROM THE PROPERTY LINE;
 - 10 FEET (3048 MM) FROM OPENINGS INTO THE BUILDING;
 - 6 FEET (1829 MM) FROM EXTERIOR WALLS AND ROOFS;
 - 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND OPENINGS
 INTO THE BUILDING WHICH ARE IN THE DIRECTION OF THE
 EXHAUST DISCHARGE;
 - 10 FEET (3048 MM) ABOVE ADJOINING GRADE.
  
 4. PROVIDE SPECIFICATIONS FOR THE EXHAUST FAN. ELECTRIC
 MOTORS DRIVING EXHAUST FANS SHALL NOT BE PLACED INSIDE
 DUCTS. FAN ROTATING ELEMENTS SHALL BE NONFERROUS OR
 NONSPARKING OR THE CASING SHALL CONSIST OF, OR BE LINED
 WITH, SUCH MATERIAL. BELTS SHALL NOT ENTER THE DUCT OR
 BOOTH UNLESS THE BELT AND PULLEY WITHIN THE DUCT ARE
 TIGHTLY ENCLOSED IN ACCORDANCE WITH FBCM 502.7.3.7.
  
 5. EAST EXTERIOR ELEVATION IDENTIFIES THE EXHAUST
 TERMINATION AS A LOUVERED VENT. THIS APPEARS TO BE AN
 UP-TURNED 90 DEGREE ELBOW, NOT A LOUVER. PLEASE
 CLARIFY. ALSO, SEE COMMENT #3 ABOVE, THIS TERMINATION
 SHALL BE A MINIMUM OF 6 FEET FROM THE EXTERIOR OF THE
 BUILDING. SHOW WHAT TYPE OF WEATHERPROOF TERMINATION IS
 TO BE USED. EXHAUST OUTLETS SHALL BE PROTECTED AGAINST
 LOCAL WEATHER CONDITIONS IN ACCORDANCE WITH FBCM 401.6
  
 6: THE MAKE-UP AIR LOVER IS REQUIRED TO HAVE A PRODUCT
 APPROVAL IN ACCORDANCE WITH FBCB 1609 AND FAC RULE
 9B-72. PROVIDE PRODUCT APPROVAL DOCUMENTATION APPROVED
 IN WRITING BY THE ARCHITECT IN ACCORDANCE WITH FBCB
 106.3.3.
  
 7. SHOW HOW THE EXTERIOR EXHAUST DUCT AND TERMINATION
 ARE TO BE SECURED AND INSTALLED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  