| 2008-10-06 16:29:11 | *****DENIED***** |
| | |
| | |
| | 1. NFPA 33, STANDARD FOR SPRAY APPLICATION USING |
| | FLAMMABLE OR COMBUSTIBLE MATERIALS, 2003 EDITION SHALL |
| | BE REFERENCED. |
| | |
| | 2. PLEASE LIST THE TYPE OF OCCUPANCY THAT THE SPRAY |
| | BOOTH IS TO BE INSTALLED. |
| | |
| | 3. LIST THE FIRE RESISTIVE RATING OF THE CONSTRUCTION |
| | ASSEMBLIES (WALLS, CEILINGS) SURROUNDING THE PAINT |
| | BOOTH. |
| | |
| | 4. SHOW THE LOCATION OF THE PAINT BOOTH IN RELATION TO |
| | MEANS OF EGRESS (DOORS, WINDOWS) THAT MEET THE |
| | REQUIREMENTS OF NFPA 101. |
| | |
| | 5. SPRAY BOOTHS SHALL BE SEPARATED FROM OTHER |
| | OPERATIONS BY A MINIMUM OF 3 FT. OR BY A WALL, |
| | PARTITION, OR FLOOR/CEILING ASSEMBLY HAVING A MINIMUM |
| | FIRE RESTIVE RATING OF 1 HOUR. |
| | |
| | 6. THE SPRAY BOOTH SHALL BE PROTECTED WITH AN APPROVED |
| | AUTOMATIC FIRE PROTECTION SYSTEM. PLEASE INDICATE THE |
| | TYPE OF SYSTEM THIS WILL BE. |
| | |
| | 7. SHOW THE LOCATION OF THE PORTABLE FIRE EXTINGUISHERS |
| | INDEPENDENT OF THE PAINT BOOTH'S SUPPRESSION SYSTEM. |
| | |
| | 8. NO SMOKING OR OPEN FLAMES SIGNS IN LARGE LETTERS ON |
| | CONTRASTING COLOR BACKGROUND SHALL BE CONSPICUOUSLY |
| | POSTED AT ALL SPRAY AREAS AND PAINT STORAGE AREAS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE/HOW THE COMMENT HAS BEEN |
| | ADDRESSED |
| | |
| | |