2008-10-06 16:29:11*****DENIED*****
  
  
 1. NFPA 33, STANDARD FOR SPRAY APPLICATION USING
 FLAMMABLE OR COMBUSTIBLE MATERIALS, 2003 EDITION SHALL
 BE REFERENCED.
  
 2. PLEASE LIST THE TYPE OF OCCUPANCY THAT THE SPRAY
 BOOTH IS TO BE INSTALLED.
  
 3. LIST THE FIRE RESISTIVE RATING OF THE CONSTRUCTION
 ASSEMBLIES (WALLS, CEILINGS) SURROUNDING THE PAINT
 BOOTH.
  
 4. SHOW THE LOCATION OF THE PAINT BOOTH IN RELATION TO
 MEANS OF EGRESS (DOORS, WINDOWS) THAT MEET THE
 REQUIREMENTS OF NFPA 101.
  
 5. SPRAY BOOTHS SHALL BE SEPARATED FROM OTHER
 OPERATIONS BY A MINIMUM OF 3 FT. OR BY A WALL,
 PARTITION, OR FLOOR/CEILING ASSEMBLY HAVING A MINIMUM
 FIRE RESTIVE RATING OF 1 HOUR.
  
 6. THE SPRAY BOOTH SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE PROTECTION SYSTEM. PLEASE INDICATE THE
 TYPE OF SYSTEM THIS WILL BE.
  
 7. SHOW THE LOCATION OF THE PORTABLE FIRE EXTINGUISHERS
 INDEPENDENT OF THE PAINT BOOTH'S SUPPRESSION SYSTEM.
  
 8. NO SMOKING OR OPEN FLAMES SIGNS IN LARGE LETTERS ON
 CONTRASTING COLOR BACKGROUND SHALL BE CONSPICUOUSLY
 POSTED AT ALL SPRAY AREAS AND PAINT STORAGE AREAS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE COMMENT HAS BEEN
 ADDRESSED
  
  