| Date |
Text |
| 2008-10-02 08:45:24 | BUILDING PLAN REVIEW |
| | PERMIT: 08090316 |
| | ADD: 2903 HILLSBORO RD |
| | CONT: TIM JOHNSON REMODELING |
| | TEL: (561)707-7058 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR |
| | PERMIT. 106.1* /2004 WEST PALM BEACH ADMINISTRATIVE |
| | CODE. |
| | |
| | 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 2) MISSING WIND DESIGN INFORMATION :1603.1.4 WIND |
| | DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 3A) WALL LOUVER |
| | |
| | 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4) SPRAY ROOM REQUIREMENTS: |
| | 416.1 GENERAL. |
| | THE PROVISIONS OF THIS SECTION SHALL APPLY TO THE |
| | CONSTRUCTION, INSTALLATION AND USE OF BUILDINGS AND |
| | STRUCTURES, OR PARTS THEREOF, FOR THE SPRAYING OF |
| | FLAMMABLE PAINTS, VARNISHES AND LACQUERS OR OTHER |
| | FLAMMABLE MATERIALS OR MIXTURES OR COMPOUNDS USED FOR |
| | PAINTING, VARNISHING, STAINING OR SIMILAR PURPOSES. |
| | SUCH CONSTRUCTION AND EQUIPMENT SHALL COMPLY WITH THE |
| | FLORIDA FIRE PREVENTION CODE . |
| | SPRAY |
| | 416.2 SPRAY ROOMS. |
| | SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS |
| | AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A |
| | 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE |
| | WATERPROOFED AND DRAINED IN AN APPROVED MANNER. |
| | |
| | 416.2.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH |
| | AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE |
| | OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO |
| | FACILITATE WASHING AND CLEANING, AND SHALL BE SO |
| | DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | 416.3 SPRAYING SPACES. |
| | SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST |
| | SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR |
| | VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL . WHERE SUCH SPACES ARE NOT SEPARATELY |
| | ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE |
| | PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS. |
| | |
| | 416.3.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE |
| | SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO |
| | CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR |
| | FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE |
| | WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO |
| | CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | 416.4 FIRE PROTECTION. |
| | AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE |
| | PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND |
| | STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH CHAPTER 9 . |
| | |
| | 5) PLEASE PROVIDE INFORMATION AS TO HOW THE EXHAUST |
| | VENT WILL BE MOUNTED TO THE BUILDING IN A HIGH WIND |
| | EVENT. 1609.6.2.2. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |