2008-10-02 08:45:24BUILDING PLAN REVIEW
 PERMIT: 08090316
 ADD: 2903 HILLSBORO RD
 CONT: TIM JOHNSON REMODELING
 TEL: (561)707-7058
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR
 PERMIT. 106.1* /2004 WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) MISSING WIND DESIGN INFORMATION :1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A) WALL LOUVER
  
 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) SPRAY ROOM REQUIREMENTS:
 416.1 GENERAL.
 THE PROVISIONS OF THIS SECTION SHALL APPLY TO THE
 CONSTRUCTION, INSTALLATION AND USE OF BUILDINGS AND
 STRUCTURES, OR PARTS THEREOF, FOR THE SPRAYING OF
 FLAMMABLE PAINTS, VARNISHES AND LACQUERS OR OTHER
 FLAMMABLE MATERIALS OR MIXTURES OR COMPOUNDS USED FOR
 PAINTING, VARNISHING, STAINING OR SIMILAR PURPOSES.
 SUCH CONSTRUCTION AND EQUIPMENT SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE .
 SPRAY
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE
 WATERPROOFED AND DRAINED IN AN APPROVED MANNER.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL . WHERE SUCH SPACES ARE NOT SEPARATELY
 ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE
 PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS.
  
 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .
  
 5) PLEASE PROVIDE INFORMATION AS TO HOW THE EXHAUST
 VENT WILL BE MOUNTED TO THE BUILDING IN A HIGH WIND
 EVENT. 1609.6.2.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved