| 2008-09-29 16:24:41 | SIGN BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. | | | | | | 1- PROVIDE NOTICE OF COMMENCEMENT AS REQUIRED BY SEC. | | | 713.13 FLORIDA STATUTE. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. UPDATE VALUATION AS REQUIRED BY SEC. 108.3 CITY | | | AMENDMENTS TO FBC 2004. VALUE TO INCLUDE ENGINEERING | | | AND CONTRACTOR FULL FEES. | | | | | | 3- PROVIDE COMPLETE SPECIFICATIONS FOR ANCHORING OF | | | LETTERS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO | | | VERIFY COMPLIANCE WITH THE WIND LOADS OF SEC. 1609 FBC | | | 2004. ENGINEERED DRAWINGS ONLY SHOW STUD. BUT, IT | | | DOESN'T SPECIFY STUD MATERIAL, DIAMETER AND LENGTH. HOW | | | MANY STUDS ARE REQUIRED PER LETTER. IN ADDITION, | | | SPECIFICATIONS ON SAME SHEET STATES THAT TYPE OF WALL | | | IS UNKNOWN. WHY IS ENGINEER CERTIFYING THAT SIGN WILL | | | RESIST 150MPH WIND LOADS IF HE DOESN'T KNOW WHAT TYPE | | | OF WALL IS HE ATTACHING THE SIGN TO. SPECIFY TYPE OF | | | WALL THAT WILL RECEIVE SIGN TO VERIFY COMPLIANCE WITH | | | PROPOSED ANCHOR TYPE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|