| Plan Review Notes For Permit 08090306 |
| Permit Number |
08090306 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-08 11:35:47 | ***DENIED*** | | | | | | 1) PLANS ILLUSTRATE CARD READERS. WORK SHALL COMPLY | | | WITH NFPA 101, SEC. 7.2.1.6.2 FOR ACCESS CONTROLLED | | | EGRESS DOORS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR | | | ACCESS CONTROL SYSTEM. | | | | | | 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|