| 2008-10-03 17:04:21 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 |
| | AND COORDINATE ALL LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE BE SURE THE TYPE OF FIXTURES, NUMBER OF FIXTURES |
| | AND WATTAGES COORDINATED WITH THE CALCULATIONS AS |
| | SHOWN. |
| | ONE EXAMPLE: THE 34WATTS INPUT REQUIRED FOR RECESSED |
| | DOWN LIGHTS IS NOT THE SAME. SHOWN AS 32WATTS ON |
| | CALCULATIONS HOWEVER THE INPUT NEEDS TO BE 34WATTS. THE |
| | COUNT OF THE 34 WATT FIXTURES IS ALSO NOT ACCURATE. |
| | |
| | ** ONE EXAMPLE GIVEN AS A BENEFIT TO DESIGN TEAM ONLY. |
| | THIS IS NOT AN EXHAUSTED LIST. |
| | |
| | 2) NOTE: ROOM 1028 IS DEFINED ON PLANS AS AN IT ROOM. |
| | IF THIS IS THE CASE PLEASE SEE THE REQUIREMENTS OF |
| | NFPA-75 AND MORE IMPORTANTLY NEC 645 FOR DISCONNECTS, |
| | ETC REQUIRED. PLEASE CLARIFY THE SHUNT TRIP IN PANEL HA |
| | IS FOR THE AHU SYSTEM FRO THE ROOM. IF THIS IS NOT AN |
| | IT ROOM, NO WIRING METHODS IN NEC 645 ARE PERMITTED AND |
| | PLACE NOTES ON PLANS ACCORDINGLY. |
| | PLEASE ALSO CHANGE ROOM DESIGNATION. |
| | |
| | 3) NOTE: PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. EXAMPLE: *LIGHTING* |
| | NOTED. |
| | 408.4 |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |