Plan Review Notes
Plan Review Notes For Permit 08090306
Permit Number 08090306
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-03 17:04:21 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2
 AND COORDINATE ALL LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE BE SURE THE TYPE OF FIXTURES, NUMBER OF FIXTURES
 AND WATTAGES COORDINATED WITH THE CALCULATIONS AS
 SHOWN.
 ONE EXAMPLE: THE 34WATTS INPUT REQUIRED FOR RECESSED
 DOWN LIGHTS IS NOT THE SAME. SHOWN AS 32WATTS ON
 CALCULATIONS HOWEVER THE INPUT NEEDS TO BE 34WATTS. THE
 COUNT OF THE 34 WATT FIXTURES IS ALSO NOT ACCURATE.
  
 ** ONE EXAMPLE GIVEN AS A BENEFIT TO DESIGN TEAM ONLY.
 THIS IS NOT AN EXHAUSTED LIST.
  
 2) NOTE: ROOM 1028 IS DEFINED ON PLANS AS AN IT ROOM.
 IF THIS IS THE CASE PLEASE SEE THE REQUIREMENTS OF
 NFPA-75 AND MORE IMPORTANTLY NEC 645 FOR DISCONNECTS,
 ETC REQUIRED. PLEASE CLARIFY THE SHUNT TRIP IN PANEL HA
 IS FOR THE AHU SYSTEM FRO THE ROOM. IF THIS IS NOT AN
 IT ROOM, NO WIRING METHODS IN NEC 645 ARE PERMITTED AND
 PLACE NOTES ON PLANS ACCORDINGLY.
 PLEASE ALSO CHANGE ROOM DESIGNATION.
  
 3) NOTE: PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. EXAMPLE: *LIGHTING*
 NOTED.
 408.4
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  