| Plan Review Notes For Permit 08090304 |
| Permit Number |
08090304 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-30 14:33:53 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. THE NUMBER OF EXIT LIGHTS SHOWN ON SHEET A2.1 AND | | | SHEET E2 DON'T CORRELATE. NO EXIT LIGHT SHOWN IN THE | | | CONFERENCE ROOM ON SHEET A2.1 AS INDICATED ON SHEET E2. | | | | | | 3. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS LOCATED | | | IN SCOPE OF WORK AREA. THESE MAY SHOWN ON THE REFLECTED | | | CEILING PLAN (SHEET A2.1). | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|