| Date |
Text |
| 2008-09-24 11:06:43 | |
| | ** DENIED REVIEW ** |
| | |
| | |
| | 1) NOTE: THE ELECTRICAL DISCONNECTS DO NOT APPEAR TO |
| | MEET 110.26 FOR HEIGHTS OR WORKING CLEARANCES. THIS IS |
| | A LIFE SAFETY ISSUE AND NEEDS TO BE VERIFIED AT THIS |
| | TIME. ONCE VERIFIED, THERE MAY BE A NEED TO RE-ARRANGE |
| | SERVICE DISCONNECTS. |
| | PLEASE SEE 110.26 ALL. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| | FOR MINIMUM REQUIRED LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE COMPLETE THE FIXTURE LEGEND FOR SPECIFIC |
| | FIXTURES, TYPES, WATTAGES ETC. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |