| 2008-09-17 12:00:25 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A6, SANITARY PLUMBING RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN ON SHEET A2. AT A MINIMUM THE |
| | SANITARY RISER SHOULD REFLECT THE FLOOR PLAN. PLEASE |
| | CORRECT THE FOLLOWING PER THE FBC-2004 PLUMBING CODE |
| | SECTION 701.1 SCOPE. |
| | |
| | A} UTIL. WASHING MACHINE AND LAUNDRY TRAY ARE BEING |
| | INDICATED IN THE WRONG PLACE. |
| | |
| | B} BATH 3, LAVATORY IS MISSING FROM THE SANITARY RISER. |
| | |
| | C} POWDER ROOM BATH IS BEING SHOWN IN THE WRONG PLACE |
| | DUE TO THE LOCATION OF ITS BRANCH FITTING OFF THE MAIN. |
| | CLEARLY INDICATE THE REQUIRED OFFSET TO THE POWDER ROOM |
| | DUE TO ITS BRANCH FITTING LOCATION. |
| | |
| | D} HER BATH, LAVATORY IS BEING INDICATED IN THE WRONG |
| | PLACE. |
| | |
| | E} MORNING BAR SINK BY THE GUEST SUITE IS MISSING FROM |
| | THE SANITARY RISER. |
| | |
| | 2. SHEET A6, SANITARY RISER: THE KITCHEN DOUBLE BOWL |
| | SINK WITH DISPOSAL AND DISHWASHER ARE BEING INDICATED |
| | WITH A WASTE ARM AND VENT THRU THE ROOF. PLEASE KNOW |
| | THAT PER TABLE 906.1, MAXIMUM DISTANCE OF FIXTURE TRAP |
| | FROM VENT WITH AN 1-1/2 TRAP AND 2" WASTE ARM CAN ONLY |
| | BE 6' FROM THE VENT. IT IS SUGGESTED THAT THE DOUBLE |
| | BOWL SINK WITH DISPOSAL AND DISHWASHER BE VENTED WITH |
| | AN AIR ADMITTANCE VALVE (STUDOR VENT) PER FBC-2004 |
| | PLUMBING SECTION 917, AIR ADMITTANCE VALVES. ALSO |
| | PLEASE CLEARLY INDICATE THE DISHWASHER DRAIN TO |
| | DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF |
| | THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD |
| | WASTE GRINDER. PER FBC-2004 PLUMBING SECTION 802.1.6 |
| | DOMESTIC DISHWASHING MACINES. |
| | |
| | 3. SHEET A2 SANITARY PLUMBING RISER INDICATES BUILDING |
| | SEWER DISCHARGE TO A SEPTIC TANK. PLEASE DELETE "SEPTIC |
| | TANK" AND ADD IN ITS PLACE "SEWER SYSTEM". PER |
| | MUNICIPAL CODE SECTION 90-123 USE OF SANITARY |
| | SEWERS.(C) SEPTIC TANKS ARE PROHIBITED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |