| 2008-09-17 15:53:07 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 2} THE A/C CONDENSERS LOCATIONS ON SHEET A7 DO NOT |
| | MATCH THE LOCATIONS ON SHEET M-1. PLEASE CORRELATE. |
| | |
| | 3} ON THE PANEL SCHEDULE, SHEET A7, THE MAXIMUM OCP FOR |
| | AHU'S #1 AND #3, EXCEEDS THE MAXIMUM RECOMMENDED BY THE |
| | MANUFACTURER ON SHEET M-1, ALSO THOSE AIR HANDLERS HEAT |
| | STRIPS ARE SPECIFIED @7500 WATTS AND ARE LISTED ON THE |
| | PANEL SCHEDULE AS 10000WATTS, CORRELATE WITH THE |
| | MECHANICAL MANUFACTURERS SPEC'S. |
| | |
| | 4} CONDENSING UNIT #4 MUST HAVE A RECEPTACLE FOR |
| | SERVICING PER 210.63. |
| | |
| | 5} 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| | SHALL HAVE BATTERY BACK UP. |
| | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN. |
| | NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |