| Notes |
| Date |
Text |
| 2008-09-19 16:20:41 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS | | | REQUIRED FOR ISSUANCE. | | | | | | 2. SEE PAGE 14. A FACTOR OF .83 IS REQUIRED FOR 3" EDGE | | | DISTANCE. | | | | | | 3. SEE PAGE 14, NOTE A1. EMBEDMENT OF 1 3/4" REQUIRED; | | | THEREFORE A 1 3/4" TAPCON DOES NOT MEET THE EMBEDMENT | | | REQUIREMENT. | | | |
|