| 2009-03-29 10:56:34 | ** DENIED REVIEW ** |
| | 3RD REVIEW |
| | |
| | 1) NOTE: AS NOTED ON PREVIOUS REVIEW, THE SYSTEM PER |
| | FBC 3006.2 IS NOT ON ELECTRICAL PLANS. THE RESPONSE |
| | LETTER MENTIONS TO SEE NOTE #1 IN LETTER HOWEVER THAT |
| | NOTE #1 WAS SPECIFIC TO CIRCUIT H-8 FROM PREVIOUS |
| | REVIEW. |
| | THIS HAS BEEN NOTED IN THE LAST THREE REVIEWS. WHERE IS |
| | THE DEDICATED CIRCUITING? WHERE THESE ON THE PANEL ARE |
| | SCHEDULES AS DEDICATED CIRCUITS? |
| | THE ONLY REVISION TO THIS NOW IS CIRCUIT H-38 WHICH IS |
| | NOT DEDICATED FOR THE FAN. IT CAN NOT BE ON WITH ANY |
| | OTHER DEVICES. |
| | THE SYSTEM NEEDS TO BE INDEPENDENT. |
| | |
| | ** A SEPARATE INFORMATIONAL; PLEASE TAKE A LOOK AT 2004 |
| | ASME-17 FOR ELEVATOR CODE REQUIREMENTS. THERE ARE |
| | SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT. |
| | |
| | 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT |
| | COMPLETE WITH ALL ELECTRICAL ITEMS ON PLANS IN THE |
| | INPUT DATA REPORT. MANY EXAMPLES WERE GIVEN ON PREVIOUS |
| | REVIEWS HOWEVER THE IDR IS STILL MISSING ELECTRICAL |
| | ITEMS. |
| | AN EXAMPLE: THERE IS A 12KW ELECTRIC WATER HEATER ON |
| | PLANS YET THE IDR IS BLANK. ANOTHER WOULD BE THE HW |
| | PIPING WHICH GOES ALONG WITH THIS. |
| | THESE ARE MINIMUMS IN THE CODE. |
| | PLEASE CORRELATE. |
| | 13-412.1.ABC.4, 13-412, 13-400.B.3 ETC |
| | |
| | *** KEEP IN MIND THERE MAY BE OTHER BUILDING COMPONENTS |
| | WHICH ARE NOT IN THE IDR WHICH MAY BE NOTED BY OTHER |
| | TRADES. |
| | |
| | 3) NOTE: SERVICE HAS BEEN REVISED. NEED TO SHOW LOAD |
| | CALCULATIONS TO BE SHOWN FOR THE NEW 800AMP MAIN. |
| | PLEASE ALSO INCLUDE LOAD ON THE HOUSE METER. THE |
| | ELEVATOR IS SHOWN BEING TAPPED FROM THE 400AMP METER |
| | ALONG WITH THE HOUSE PANEL. THE ONLY LOAD SHOWN FOR THE |
| | HOUSE METER IS THE LOAD ON THE HOUSE PANEL. |
| | NEC220 |
| | |
| | 4) NOTE: PLEASE BE SURE WHEN SEALING THE PLANS ( SEE |
| | NEW SHEETS) THE SEAL IS CLEAR AND VISIBLE. THE NEW |
| | SHEETS IN SETS ARE VERY FAINT AND SOME CAN NOT BE SEEN |
| | EVEN USING LEAD RUB. |
| | FS 471.0221. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |