| 2009-02-09 09:50:04 | ** DENIED 2ND REVIEW ** |
| | |
| | ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF |
| | ADDRESSING FROM THE PREVIOUS REVIEWS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE CIRCUITING IN THE ELEVATOR |
| | MACHINE ROOM AND ELEVATOR ARE SHOWN NOW ON THE SAME |
| | CIRCUIT FOR H-8. PANEL SCHEDULE STATES RECEPTS/LIGHTS |
| | FOR ELEVATOR PIT HOWEVER BASED ON THE PLANS THESE ARE |
| | BEING SHARD INTO OTHER AREAS WHICH IS NOT PERMITTED. |
| | PLEASE SEE 680.22-680.24. DEDICATED CIRCUITS ARE |
| | REQUIRED FOR EACH OF THE SPACES AS LISTED INCLUDING FOR |
| | THE ELEVATOR CAR ITSELF. |
| | PLEASE SEE THE NEXT COMMENT AS THIS IS AFFECT BY THE |
| | SAME NOTE. |
| | |
| | 2) NOTE: PLEASE SEE FBC 3006.2 WITH THE REQUIRED |
| | INDEPENDENT SYSTEM FOR THE ELEVATOR MACHINE ROOM. THIS |
| | WOULD REQUIRE DEDICATED CIRCUITING AS NOTED ABOVE IN |
| | COMMENT #1. ( NOTED PREVIOUS REVIEW ) |
| | |
| | 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH |
| | RESPECT TO FBC CHAPTER 13. COMPLIANCE FOR MINIMUM HAS |
| | NOT BEEN MET. |
| | |
| | A) THE SQUARE FOOTAGE ON PLANS AND CALCULATIONS |
| | SUBMITTED DO NOT COORDINATE. |
| | |
| | B) THE PLANS CONTAINS A METHOD *B* TABLE CALCULATION |
| | FOR SPACE BY SPACE. IT IS NOT PERMISSIBLE TO MIX |
| | METHODS OF CALCULATIONS. PLEASE SEE 13-415.2.ABC.1 |
| | |
| | C) PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT |
| | ALSO NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. THE |
| | INPUT DATA REPORT WILL BE NOTED AS IDR ON THE REMAINDER |
| | OF THIS COMMENT. |
| | THERE ARE STILL LIGHTING FIXTURES ON PLANS WHICH ARE |
| | NOT IN THE IDR OR FIXTURE WATTAGES WHICH DO NOT |
| | COORDINATE. |
| | |
| | FOR EXAMPLE: PLEASE SEE THE COUNT ON THE EXTERIOR |
| | LIGHTS, WATTAGES DO NOT COORDINATE. THE IDR ONLY |
| | INDICATE 2-500WATT FIXTURES AND 8-46 WATT FIXTURES. |
| | THERE ARE ACTUALLY MORE FIXTURES ON PLANS BY COUNT AND |
| | WATTAGE. |
| | |
| | FOR EXAMPLE: INTERIOR LIGHT FIXTURES SHALL INCLUDE ALL |
| | AREAS. BASED ON THE IDR, IT ONLY LIST TWO DIFFERENT |
| | TYPE OF FIXTURES. BASED ON THE PLANS AND THE FIXTURE |
| | LEGEND THIS IS NOT THE CASE. |
| | |
| | FOR EXAMPLE: FIXTURES NEED TO BE SPECIFIC. MOST |
| | FIXTURES STATE *TBD* WHICH THE VA RATING CAN NOT BE |
| | VERIFIED. PLEASE SELECT SPECIFIC FIXTURES. THESE MAY |
| | ALWAYS BE REVISED AT A LATER DATE IF A PRODUCT CHANGES. |
| | THE GOAL IS AT LEAST TO MEET THE MINIMUM CODES. |
| | *D* FIXTURES ARE SHOWN ON PLANS HOWEVER HAVE DIFFERENT |
| | SYMBOLS. WHEN LOOKING AT THE SYMBOL LEGEND YOU WILL SEE |
| | EACH OF THESE ARE ACTUALLY DIFFERENT. ONE IS 58VA AND |
| | THE OTHER 29 VA. |
| | |
| | |
| | *** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT TO |
| | HELP. THESE MAY NOT BE ALL ITEMS. IT IS IMPORTANT TO |
| | FIGURE HOW CALCULATIONS WILL BE DONE FOR EACH SPACE OR |
| | AS PART OF THE BUILDING. |
| | PLEAS BE SURE TO GO OVER AND CALL WITH ANY COMMENTS OR |
| | QUESTIONS FOR COORDINATION. |
| | 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3. |
| | |
| | 4) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE CONTROLS |
| | REQUIRED FOR CONFERENCE ROOM. ( NOTED ON PREVIOUS |
| | REVIEW) |
| | |
| | 5) NOTE: BASED ON A COMPLETE REVISED ELECTRICAL RISER, |
| | PLEASE SEE 230.70. THERE ARE UNPROTECTED CONDUCTORS |
| | INSIDE THE BUILDING WHICH IS NOT PERMITTED. THE CODE |
| | SECTION GIVEN DOES NOT GIVE AN AMOUNT PERMITTED. |
| | THE OLD PALM BEACH COUNTY AND CITY OF WEST PALM BEACH |
| | TECHNICAL AMENDMENTS PERMITTED UP TO 8FT, HOWEVER AS |
| | THE OLDER CODE CHANGED THE TECHNICAL AMENDMENTS WENT |
| | AWAY. SOME MUNICIPALITIES DO NOT PERMIT ANY UNPROTECTED |
| | CONDUCTORS INSIDE THE BUILDING. |
| | THE AMOUNT AS SHOWN ON PLANS IS OVER. PLEASE ADJUST |
| | DESIGN. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| 2009-02-06 17:00:40 | REVIEW TO CONTINUE. REVIEW WILL GO INTO A FAILED STATUS |
| | ONCE COMPLETE. SOME NOTES FROM PREVIOUS REVIEW AND |
| | MEETING STILL NEED TO BE ADDRESSED. |