| Date |
Text |
| 2008-09-15 13:37:04 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 2. SUBMIT MANUF. SPECIFICTIONS FOR THE BUBBLER SHOWING |
| | CONFORMANCE WITH ASME A112.19.1M, ASME A112.19.2M OR |
| | ASME A112.19.9M AS WELL AS NSF61 SECTION 9. SECTION |
| | 410. |
| | |
| | 3. SHT A-1.02 A WASH MACHINE CONNECTION IS REQUIRED IN |
| | THE UNIT WITH ROOMS 201, 202 & 203. TABLE 403.1. |
| | |
| | 4. SHT A-5.01 DETAIL (1), LAV SHALL BE MINIMUM 15" OFF |
| | THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE |
| | CENTERED ON THE REQUIRED 30" WIDTH OF THE CLEAR FLOOR |
| | SPACE. SECTION 11-4.19.3 & FIGURE 32. |
| | |
| | 5. SHT A-5.01 DETAIL (2), THE DISPENSER SHALL BE |
| | MINIMUM 19" OFF THE FLOOR TO THE CENTERLINE. DETAIL |
| | SHOWS 17" TO CENTERLINE. SECTION 11-4.19.6 & FIGURE |
| | 29(B). |
| | |
| | 6. SHT A-5.01 SHOW COMPLIANCE WITH SECTION 11-4.19.5 |
| | FAUCETS. |
| | |
| | 7. SHT A-5.01 DETAIL (4), INDICATES "OPTIONAL CUP |
| | HOLDER". IF THE CUP HOLDER IS NOT REQUIRED, THEN SHOW |
| | COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 8. SHT P-1.01 AN RPZV BACKFLOW IS REQUIRED ON THE WATER |
| | SERVICE TO THE BUSINESS OCCUPANCY. SECTION 608.13.3. |
| | |
| | 9. SHT P-1.02 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. THE CLEANOUT SHOWN ON THE RISER |
| | DIAGRAM DOWNSTREAM OF THE LAST TWO 3" RISERS IS NOT |
| | SHOWN ON THE FLOOR PLAN. -- RISER DOES NOT SHOW THE |
| | VENT THRU THE ROOF FOR THE FIXTURES ON THE FIRST FLOOR. |
| | PLEASE CORRELATE. SECTIONS 106.1.1, 708.3.3 & 903.3. |
| | |
| | 10. SHT P-1.02 NOTE FOR WATER HEATER AT THE TOP OF THE |
| | SHEET IS NOT LEGIBLE. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL |
| | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS (REQD BY |
| | SECTION 604.9) ETC. SECTION 105.3.5.1.3 & 601.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |