| 2008-10-02 12:14:18 | BUILDING PLAN REVIEW |
| | PERMIT: 08090247 |
| | ADD: 501 N ROSEMARY AVE |
| | CONT: NUJAK DEVELOPMENT |
| | TEL: (863)686-1565 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 2) SHEET A0.00 CODE ANALYSIS INDICATES THIS BUILDING IS |
| | TO BE A TYPE III-B BUILDING AND A LEVEL III ALTERATION, |
| | MIXED OCCUPANCY WITH A BUSINESS OCCUPANCY FIRST FLOOR |
| | AND R-2 RESIDENCY SECOND FLOOR. |
| | SHEET A-1.01 ALSO INDICATES THE PROPERTY LINE ON THE |
| | WEST SIDE OF THE PROPERTY TO BE APPROXIMATELY 3'-0" |
| | AWAY. THE SURVEY PROVIDES A DIMENSION AT THE NORTHWEST |
| | CORNER OF THE BUILDING INDICATING |
| | A DISTANCE OF 2.90' AWAY FROM THE PROPERTY LINE. LEVEL |
| | III ALTERATIONS SECTION 705.1 THE MEANS OF EGRESS SHALL |
| | COMPLY WITH THE REQUIREMENTS OF SECTION 605 EXCEPT AS |
| | MODIFIED IN SECTIONS 705.2 AND 705.3. UNDER LEVEL II |
| | SECTION 605.1 THE REQUIREMENTS OF THIS SECTION SHALL BE |
| | LIMITED TO WORK AREAS THAT INCLUDE EXITS OR CORRIDORS |
| | SHARED BY MORE THAN ONE TENANT WITHIN THE WORK AREA IN |
| | WHICH LEVEL 2 ALTERATIONS ARE BEING PREFORMED, AND |
| | WHERE SPECIFIED THEY SHALL APPLY THROUGHOUT THE FLOOR |
| | ON WHICH THE WORK AREAS ARE LOCATED OR OTHERWISE BEYOND |
| | THE WORK AREA. |
| | |
| | 2A) WITH THIS BEING A LEVEL III ALTERATION THE EXTERIOR |
| | STAIRWAY BEING REPAIRED AND RELOCATED BASICALLY IN THE |
| | SAME LOCATION , PLEASE PROVIDE COMPLIANCE WITH 1022.5 . |
| | EXTERIOR EXIT STAIRWAYS SHALL BE LOCATED IN ACCORDANCE |
| | WITH SECTION 1023.3. |
| | 1023.3 EXIT DISCHARGE LOCATION. |
| | EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE |
| | LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT |
| | LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS |
| | THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE |
| | PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE |
| | SEPARATION DISTANCE. |
| | |
| | 2B) THE SECOND ISSUE WITH NOT KNOWING THE DISTANCE FROM |
| | THE PROPERTY LINE AT THE SECOND FLOOR DOOR OPENING IS |
| | IN TABLE 704.8 FOR UNPROTECTED OPENINGS 0-3-0? ZERO |
| | OPENINGS IN THE WALL LINE. |
| | |
| | 2C) SHEET A-1.03 INDICATE A 5?X5? DOWNSPOUT, THE SITE |
| | PLAN INDICATES A 6?-0? HIGH SECURITY FENCE ALONG THE |
| | SAME PROPERTY LINE AND THE SURVEY INDICATES FROM THE |
| | BUILDING TO PROPERTY LINE A DISTANCE OF 2.90?. HOW WILL |
| | SECTION 1009.1EXCEPTION# 1 REQUIRING A 36? WIDE STAIR? |
| | |
| | 2D) THE OTHER ISSUE IS WITH THE 5?X5? DOWNSPOUT, HOW |
| | WILL SECTION 1009.11.7 PROJECTIONS INTO THE REQUIRED |
| | WIDTH AT EACH HANDRAIL SHALL NOT EXCEED 4.5 INCHES AT |
| | OR BELOW THE HANDRAIL HEIGHT. NOTE HANDRAILS ARE TO BE |
| | CONTINUOUS SEE 1009.11.4 CONTINUITY. |
| | |
| | 2E) THE PLANS FAIL TO INDICATE HANDRAILS AT EACH SIDE |
| | OF THE STAIRS. 1009.11. |
| | |
| | 3) SHEET A-1.01 DOOR# 115-1 MACHINE ROOM, AGAIN THIS |
| | NEW ADDITION WALL LINES UP WITH THE EXISTING WALL THAT |
| | IS 2.90? FROM THE PROPERTY LINE. TABLE 704.8 THAT DOES |
| | NOT ALLOW OPENINGS UNTIL GRATER THAN 5.0? FROM THE |
| | PROPERTY LINE FOR UNPROTECTED OPENINGS. ALSO NOTE THIS |
| | DOOR NEEDS TO BE A 1-HR RATED DOOR AS TO 3006.4. THE |
| | ONE HR RATING WOULD ALLOW UNDER PROTECTED OPENINGS 15% |
| | ALLOWABLE OPENINGS AT DISTANCES OF 3?-0? AND GREATER. |
| | THE OTHER ISSUE IS THE DOOR SWING IS OVER THE ALLOWABLE |
| | EGRESS PATH. 1008.1.8.8. |
| | |
| | 4) SHEET A-1.02 WINDOW OPENING 18A IS UNPROTECTED, IS |
| | AGAIN LESS THAN 5?-0? FROM THE PROPERTY LINE AND NOT |
| | ALLOWED TABLE 704.8. |
| | |
| | 5) SHEET A-3.01 WEST ELEVATION INDICATES A LOUVERS ON |
| | THIS ELEVATION AGAIN UNPROTECTED OPENINGS WOULD NOT BE |
| | ALLOWED WITH UNPROTECTED OPENINGS, PLEASE SEE TABLE |
| | 704.8 FOR UNPROTECTED OPENINGS AND FOR PROTECTED |
| | OPENINGS. |
| | |
| | 6) THIS BUILDING DOES NOT PROVIDE ANY INFORMATION AS TO |
| | FIRE SPRINKLERS, SO IT IS ASSUMED TO BE AN |
| | UN-SPRINKLERED BUILDING. WITH THE R-2 OCCUPANCY AND THE |
| | ADDITION OF THE ELEVATOR THE REQUIREMENT FOR A AREA OF |
| | RESCUE ASSISTANCE NECESSARY. PLEASE REVIEW ALL THE |
| | REQUIREMENTS OF 11-4.3.11(1-3). |
| | |
| | 6A) PLEASE INDICATE IF THE AREA OF RESCUE ASSISTANCE |
| | WILL BE LOCATED ON THE INTERIOR OF THE BUILDING OR IF |
| | IT WILL BE LOCATED ON THE EXTERIOR 2ND FLOOR LANDING OF |
| | THE BUILDING, AND NEEDING TO HAVE FIRE RATED WINDOWS |
| | AND DOORS. IN EITHER CASE PLEASE PROVIDE THE REQUIRED |
| | CLEAR FLOOR SPACE REQUIRED FOR THE AREA OF RESCUE |
| | ASSISTANCE AND THE MEANS OF EGRESS |
| | |
| | 6B) PLEASE ALSO TAKE NOTE OF THE REQUIRED 48? CLEAR |
| | BETWEEN HANDRAILS, |
| | 11-4.3.11.3. |
| | |
| | 7) SHEET A-1.02 THE SECOND STORY LANDING INDICATES A |
| | SCUPPER LOCATED AT FLOOR LEVEL TO DRAIN WATER FROM THE |
| | LANDING. THE WATER THAT DRAINS FROM THE SCUPPER LANDS |
| | DIRECTLY ON TO THE STAIRS BELOW, PLEASE PROVIDE |
| | COMPLIANCE WITH 1009.5.2 OUTDOOR CONDITIONS. |
| | |
| | 8) SHEET A-1.03 ROOF PLAN INDICATES ?GAF LIBERTY OR |
| | APPROVED EQUAL?, 106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 9) SHEET A-4.01 S-3.02 BOTH INDICATE A NEW SECOND STORY |
| | EPICORE CONCRETE PRE-ENGINEERED FLOOR SYSTEM, PLEASE |
| | PROVIDE ADDITIONAL INFORMATION ARE SHOP DRAWINGS BEING |
| | CREATED, INDICATING OF SPANS, LOADS TO BE IMPOSED, |
| | REINFORCING AND SHORING. 1905, 1907. |
| | |
| | 10) PLEASE PROVIDE HOURLY RATING FOR THE EPICORE |
| | CONCRETE FLOOR SYSTEM, A 2HR FIRE RATING WILL BE |
| | REQUIRED BETWEEN THE R-2 OCCUPANCY AND BUSINESS |
| | OCCUPANCY BELOW. SEE TABLE 302.3.2& 712.4, ALSO PROVIDE |
| | FIRE RESISTANCE RATED ASSEMBLIES FOR THE PENETRATION OF |
| | THE SECOND STORY FLOOR ASSEMBLIES, 712.4.1. |
| | |
| | 11) PLANS FAIL TO PROVIDE FLOOR/CEILING ASSEMBLIES |
| | SOUND RATING AS REQUIRED BY 1207.3. STRUCTURE-BORNE |
| | SOUND. FLOOR/ CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL |
| | HAVE AN IMPACT INSULATION CLASS RATING OF NOT LESS THAN |
| | 50(45IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 12) SHEET A-1.02 WALL TYPE# 8 FAILS TO PROVIDE A STC |
| | RATING OF 50, 1207.2 AIR-BORNE SOUND. |
| | |
| | 13) SHEET A-2.01 SECOND STORY CORRIDOR REFLECTED |
| | CEILING PLAN DOES NOT INDICATE THE EXIT SIGNS , 1006.3. |
| | |
| | 14) PLANS S-1.01 INDICATE THE USE OF HELICAL PIER UNDER |
| | PINNING OF FOUNDATION, PLEASE PROVIDE SOILS REPORT . |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | |
| | 15) SHEET S-0.01 IS USING THE WRONG VERSION OF THE |
| | ASCE-7-05. |
| | 2004 FBC 1609.1.1 & CHAPTER 35 REFERENCED STANDARDS |
| | RECOGNIZES ASCE 7-02 . ALSO 1603.1.4 WIND DESIGN DATA. |
| | |
| | 16) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS:\ |
| | 16A) SINGLE HUNG WINDOWS |
| | 16B) FIXED, STOREFRONT |
| | 16C) MULLIONS |
| | 16D) EXTERIOR GLAZED DOORS |
| | 16E) EXTERIOR METAL DOORS |
| | 16F) EXTERIOR LOUVER DOORS |
| | 16G) WALL LOUVERS |
| | 16H) LINTELS |
| | 16I) ROOFING ASSEMBLIES, FLAT ROOF, UNDERLAYMENT?S, |
| | TILE AND ADHESIVES |
| | |
| | 17) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 18) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 19) THE INPUT DATA REPORT FROM THE ENERGY CALCS DOES |
| | NOT MATCH THE PLANS, THE COUNT ON THE WINDOWS AND THE |
| | SQUARE FOOTAGE ARE OFF AND THE DOOR TYPE AND DOOR COUNT |
| | DOES NOT MATCH THAT OF THE PLANS. THERE ARE A TOTAL OF |
| | 5 DOORS THAT LEAD INTO THE BUSINESS OFFICE PLEASE |
| | CORRECT. MISSING NORTH DOOR 101-2 AND PAIR OF DOORS |
| | 102-1. |
| | |
| | 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC |
| | |
| | |