| Plan Review Notes For Permit 08090228 |
| Permit Number |
08090228 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-18 15:07:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. PROVIDE INFORMATION REGARDING THE BUILDING LOCATION | | | TO CLARIFY USE OF EXPOSURE B. SEE FBC1609.4; NOTE THAT | | | THE DEFINITION FOR EXPOSURE C HAS CHANGED EFFECTIVE | | | JULY 1, 2007. | | | | | | 2. SHOW ALL EXIT DOORS ON THE FLOOR PLAN. EXITS CANNOT | | | BE BLOCKED WITH STORM PANELS, FBC1003.6. | | | | | | 3. OPENING 1, A DESIGN PRESSURE OF -34.9 REQUIRES USE | | | OF THE ROW -44.2, SEE PAGE 4. SEE ANCHOR NOTES, PAGE 6, | | | ITEM2 - "ENTER ANCHOR SCHEDULE BASED ON THE EXISTING | | | STRUCTURE MATERIAL ANCHOR TYPE AND EDGE DISTANCE. | | | SELECT DESIGN LOAD GREATER THAN OR EQUAL TO NEGATIVE | | | DESIGN LOAD ON SHUTTER." A DESIGN PRESSURE OF -34.9 IS | | | CONSIDERED A GREATER NEGATIVE DESIGN PRESSURE THAN -33. | | | THIS COMMENT APPLIES TO OTHER OPENINGS (INCORRECT ROW | | | USED; ALL PRESSURES FOR THIS JOB ARE GREATER THAN | | | -33PSF). FBC R301. | | | |
|