Plan Review Notes
Plan Review Notes For Permit 08090223
Permit Number 08090223
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-29 16:38:04BUILDING PLAN REVIEW
 PERMIT: 08090223
 ADD: 6910 S DIXIE HWY.
 CONT: SULLIVAN BUILDERS OF FLORIDA
 TEL: (561)310-1899
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) I INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) SHEET A-1 THE FRONT ENTRY PORCH HAS A 6 INCH DROP
 MAKING IT IMPASSIBLE FOR WHEEL CHAIR USERS. 11-4.3.2(1)
 AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY OF
 THE SITE SHALL BE PROVIDED FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND ACCESSIBLE PASSENGER
 LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE. THE ACCESSIBLE
 ROUTE SHALL, TO THE MAXIMUM EXTENT FEASIBLE, COINCIDE
 WITH THE ROUTE FOR THE GENERAL PUBLIC.
  
 3) SHEET S-3 IS MISSING THE WIND DESIGN CRITERIA:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 4) SHEET A-2 INDICATES THE PORCH TO BE A STUCCO FINISH,
 S-1 DETAIL# 3 DOES NOT PROVIDE INFORMATION AS TO THE
 TYPE OF SUB-BASE THE STUCCO WILL BE ADHERED TOO ( WIRE
 LATH?) NOR THE WEIGHT OR GAUGE OF WIRE LATH NOR TYPE OF
 LATH TO BE INSTALLED. 2510.3/ ASTM C1063. INSTALATION
 OF LATH AND FURRING CEMENT STUCCO PLASTER.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.