| Plan Review Notes For Permit 08090201 |
| Permit Number |
08090201 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-30 16:54:23 | REDLINED PLANS | | | | | | LOADS FOR DINING ROOM WERE NOT ADDED PER | | | 210.52B1,210.11C1,220.52 AS NOTED ON PREVIOUS REVIEW. | | | THIS ADDITIONAL LOAD OF 1500VA WILL NOT AFFECT THE | | | SERVICE HOWEVER WILL NEED TO BE REVISED BEFORE FINAL. | | | IF THERE ARE REVISIONS MADE BEFORE ROUGH, PLEASE REVISE | | | AT THAT TIME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CONTACT. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH |
|