| Date |
Text |
| 2008-09-15 16:57:57 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE APPLICABLE BUILDING CODE AND THE CORRECT |
| | EDITION OF ASCE 7 ON THE PLANS. SEE 2004 FBC AND ASCE |
| | 4-02. |
| | |
| | 2) NOTE 2 ON SHEET 1 OF THE PLANS SPECIFIES REPLACE ALL |
| | DOORS. SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE |
| | DOORS. RULE 9B-72. |
| | |
| | 3) PLEASE CLARIFY ON THE PLANS IF THE OVERHEAD GARAGE |
| | DOOR IS BEING REPLACED. IF IT IS, SUBMIT PRODUCT |
| | APPROVALS. |
| | |
| | 4) THE MEAN ROOF HEIGHT ON SHEET 1 IS INCORRECT. MEAN |
| | ROOF HEIGHT IS THE DISTANCE FROM GRADE TO THE AVERAGE |
| | HEIGHT OF THE SLOPED ROOF. SEE FBC R202 FOR BUILDING |
| | HEIGHT AND MEAN ROOF HEIGHT. |
| | |
| | 5) SPECIFY THE CORRECT ROOF SLOPE ON SHEET 1. ROOF IS |
| | NOT FLAT. FBC R301.2.1 |
| | |
| | 6) PRODUCT APPROVALS WERE SUBMITTED FOR DOUBLE HUNG |
| | WINDOWS AND THE PLANS SPECIFY ALL SINGLE HUNG WINDOWS. |
| | PLEASE CLARIFY. |
| | |
| | 7) THE PRODUCT APPROVAL STATE COVERSHEET FOR THE DOUBLE |
| | HUNG WINDOWS IS NOT THE CORRECT ONE. IT IS FOR THE 2007 |
| | FBC AND IT HAS A PENDING STATUS. THE ONE FOR THE 2004 |
| | FBC IS REQUIRED. DCA RULE 9B-72. |
| | |
| | 8) THE MINIMUM WALL INSULATION FOR A 2 X 6 WALL IS R-19 |
| | PER FBC 13-600. REVISE THE R VALUE SPECIFIED WALL |
| | SECTION B ON SHEET 2. |
| | |
| | 9) PROVIDE A STRUCTURAL DETAIL OF THE BAY WINDOW |
| | INDICATING HOW THE DOUBLE 2 X 8 HEADER ABOVE THE |
| | WINDOWS WILL BE SUPPORTED AND HOW THEY WILL BE ATTACHED |
| | TO THE EXISTING TIE BEAM. SPECIFY HOW LOADS WILL BE |
| | TRANSFERRED TO THE FOUNDATION. FBC R301.1. |
| | |
| | 10) SPECIFY THE REQUIRED LOAD BEARING CAPACITY OF THE |
| | SOIL ON THE PLANS FOR THE NEW BAY WINDOW FOUNDATION. |
| | FBC R 403.1 |
| | |
| | 11) SHOW COMPLIANCE WITH R320.1 FOR PROTECTION AGAINST |
| | TERMITES ON THE PLANS AT THE NEW BAY WINDOW. |
| | |
| | 12) IF THE DOORS AND OVERHEAD GARAGE DOOR ARE BEING |
| | REPLACED SPECIFY THE POSITIVE AND NEGATIVE OPENING |
| | PRESSURES FOR THEM ON THE PLANS. FBC R301.2.1 |
| | |
| | 13) THE VALUE OF THE WORK SPECIFIED ON THE APPLICATION |
| | APPEARS TO BE LOW. THE VALUE IS TO INCLUDE THE COST OF |
| | MATERIALS, LABOR, ELECTRIC, PLUMBING, FIXTURES, |
| | CABINETS, DESIGN COSTS, OVERHEAD AND PROFIT AS A |
| | CONTRACTOR WOULD CHARGE. PLEASE ADJUST THE VALUE ON THE |
| | APPLICATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |