| Date |
Text |
| 2008-09-10 08:18:46 | 2004 FLORIDA BUILDING CODE W/2007 REVISIONS & |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE 2004 FBC |
| | |
| | DENIED |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | ____ 1.) EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| | BARRIER REQUIRED FS553.844(5)(A). PROVIDE INFORMATION |
| | (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU |
| | WILL COMPLY WITH THIS REQUIREMENT. INFORMATION IS |
| | AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION. |
| | |
| | ____ 2.) CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| | MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| | EACH ROOF TYPE |
| | |
| | ____ 3.) FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72. WWW.FLORIDABUILDING.ORG |
| | |
| | ___X__ 4.) FOR THE FLAT ROOF, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING. ALSO INDICATE WHICH FASTENER |
| | AND DESIGN PRESSURE YOU ARE USING IF THE OPTIONS HAVE |
| | DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | ___X__ 5.) FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. THIS IS TO BE |
| | EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED ON |
| | LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB SHEET). |
| | |
| | __X__ 6.) ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING. IF YOU SELECT FOAM |
| | ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| | |
| | ____ 7.) SEE PRODUCT LIMITATION #7. CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | |
| | PROVISO ? MECHANICAL EQUIPMENT TO COMPLY WITH FBC |
| | EB511, FBC1509.7. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |